Bms Points List - Greenheck Grease Trapper ESP Installation, Operation And Maintenance Manual

Kitchen exhaust pollution control system
Table of Contents

Advertisement

Grease Trapper ESP v2.00 Modbus / BACnet
BACnet Device Instance: 77000 (default)
Analog = AV, Integer = AV, Digital = BV
Type
Instance
Name
Analog
20
Exhaust_Fan_Speed
Analog
21
BMS_Exhaust_Fan_Speed
Digital
101
Remote_Enable
Digital
102
Fire_Status
Digital
103
Wash_Enable
Digital
104
Detergent_Low
Digital
105
Exhaust_Fan_Fault
Digital
106
Door_Switches
Digital
130
Exhaust_Active
Digital
131
Pass1_Power_Supply
Digital
132
Pass2_Power_Supply
Digital
133
Pass3_Power_Supply
Digital
134
Wash_Sequence_Active
®
Modbus - RTU/TCP
Address: 1 (default)
Units
Register
percent
40021
percent
40022
Inactive
Active
Text
Text
Off
On
10102
Off
On
10103
Off
On
10104
Off
On
10105
Off
On
10106
Off
On
10107
Off
On
10108
Off
On
10109
Off
On
10132
Off
On
10133
Off
On
10134
Grease Trapper ESP™ Kitchen Exhaust Pollution Control System
®
Points List
Read
Description
Write
R
Exhaust Fan Speed Percentage
R/W
BMS Exhaust Fan Speed Percentage
R/W
Remote Fan Enable (0: Off; 1: On)
R
Fire System Status (0: Ok; 1: Fire)
R/W
Wash Enable (0: Off; 1: On)
R
Detergent Status (0: Ok; 1: Empty)
R
Exhaust Fan Fault
R
Door Interlock Switches (1: Ok; 0: Door Open)
R
Exhaust Fan Status (0: Off; 1: On)
R
Power Supply Pass 1 Status (0: Off; 1: On)
R
Power Supply Pass 2 Status (0: Off; 1: On)
R
Power Supply Pass 3 Status (0: Off; 1: On)
R
Wash Status (0: Off; 1: Wash Cycle Active)
29