Wash Water Plumbing Schematic
STANDARD UNIT
SOLID FUEL UNIT
DETERGENT DISPENSER ASSEMBLY
34
Grease Trapper ESP™ Kitchen Exhaust Pollution Control System
(not to scale)
Plumbing Notes:
1. Trapped drain line water column
to be sized for total system loss
+ 1.0 in. wg
Drain shall be plumbed to an
approved grease interceptor.
2. Water supply and drain piping
exposed to freezing must be
trace heated and insulated.
3. All piping, backflow preventer,
pressure gauges, ball valves
and solenoid valves (24 VAC)
are provided by others.
4. All solenoid valves provided in
the field shall be equipped for
outdoor or indoor environment,
based on whether the unit is
mounted indoors or outdoors.
Detergent Dispenser Notes:
1. Detergent dispenser must be located
indoors in a freeze proof area.
These components must also be
located in an area convenient for
monitoring/servicing.
2. Reservoir shall be polypropylene with
removable lid.
3. Maximum allowable horizontal
distance from detergent pump to unit
= 30 feet.
4. Maximum allowable vertical distance
from detergent pump to unit = 30 feet.
®