C.

Service

C.
Service
a. System Information
Information
Greenheck Fan Corp.
Version:
2.00.000
Date
09/21/20
Bios:
6.40
11/17/15
Boot:
5.02
09/30/13
C.
Service
b. Power Supply
Power Supply Settings 1
Power Supply Operating
Voltage (JC062)
Pass1:
3.0vdc
(12.0kV)
Pass2:
3.0vdc
(12.0kV)
Pass3:
3.0vdc
(12.0kV)
Power Supply Settings 2
Power supply initial reset
attempts before alarm: 15
Power Supply Settings 3
Power supply alarm
reset delay: 10 min
C.
Service
c. Wash Settings
Wash Settings 1
Pre-Soak:
180 sec
Detergent:
60 sec
Soak:
180 sec
Rinse:
240 sec
Dry:
60 min
Drain Time:
60 sec
16
Grease Trapper ESP™ Kitchen Exhaust Pollution Control System
The Service menu allows the user to access several sub-menus regarding controller
information, controller overrides, operating hours, BMS configuration, I/O manual
management and wash settings. By accessing the BMS Configuration sub-menu,
the user can adjust BMS protocol settings. (BACnet®, LonWorks®, Modbus)
The System Information sub-menu displays information about the controller and
the program loaded on the controller.
t
his sCrEEn shows vErsion
'
to thE ControllEr
s FirmwarE and oPErating systEm
The Power Supply sub-menu allows the user to view and adjust the power supply
settings.
t
his sCrEEn allows thE UsEr to viEw
thE PowEr sUPPliEs and thE CorrEsPonding k
This should only be adjusted on factory advisement only. Default is 3.0vdc (12kV).
If provided with JC099 power supplies, control voltage is not
adjustable (fixed 12kV operating voltage).
t
his sCrEEn allows thE UsEr to adjUst
UPon a FaUlt bEForE EntEring alarm
Default is 15 attempts.
This screen is not visible if provided with JC099 power supplies.
t
his sCrEEn allows thE UsEr to adjUst PowEr sUPPly rEsEt dElay aFtEr a
PowEr sUPPly alarm has oCCUrrEd
Default is 10 minutes.
This screen is not visible if provided with JC099 power supplies.
The Wash Settings sub-menu allows the user to view and adjust the wash times.
t
his sCrEEn allows thE UsEr to adjUst sEttings For a Unit wash
timEs arE ProvidEd on PagE
Pre-Soak: Time for spraying cell(s) with water.
Detergent: Time for spraying cell(s) with water with detergent injected into the
water line.
Soak: Time to allow the cells to soak (water and detergent stop).
Rinse: Time for spraying the cell(s) with water to remove debris and detergent.
Drain: Time to drain the remainder of the water in the unit before starting the dry
portion of the wash cycle.
Dry: Time for turning on the fan after a wash to dry out the cells.
,
boot and bios inFormation
/