Service Password Screen
NOTE
The Service Password must be entered to access the
SETTINGS, CONFIGURATION and INFORMATION
screen. The default service password is 1000.
Service Password Verification Required
Insert Password:
For technical support, please call: 1-800-371-6858.
Have your serial number ready.
Active Alarms Example
ACTIVE ALARMS
DATE/TIME
3/17/2018 11:12:25 AM
Fire Detected - Fire system discharged or issue with microswitch (terminals C1 & NC1).
3/17/2018 11:12:16 AM
Exhaust Fan Alarm - Check exhaust motor starter(s) or VFD(s) for fault.
General Information
Any field surrounded by a box with a white fill indicates
that it is editable.
If an editable field displays a numerical value and the
user taps the field, a number keypad will display. After
entering the desired value, press the Enter button.
If the editable field is an alphanumeric value, a standard
keyboard will display. After entering the desired value,
press the Enter button.
The field may also display a multiple choice ON/OFF, or
a checkmark box. For the ON/OFF fields, press the box
opposite of the checked box to change the option from
either OFF to ON or vice versa.
SETTINGS, CONFIGURATION & INFORMATION
SETTINGS
CONFIGURATION
FAN SETTINGS
DATE/TIME
POWER SUPPLY
FAN SCHEDULE
SETTINGS
GENERAL WASH
SETTINGS
24
Grease Trapper ESP™ Kitchen Exhaust Pollution Control System
0
VERIFY
DESCRIPTION
RESET ALARMS
INFORMATION
SYSTEM
ALARMS
Settings
• Fan Settings
FAN SETTINGS
AUTO FAN OFF:
YES
RUN HOURS:
1
NOTE: THIS WILL ONLY SHUT THE FAN OFF IF THE FAN
WAS POWERED ON BY THE KEYPAD. THIS WILL NOT
OVERRIDE THE FAN ENABLE INPUT (RE1A AND RE-1B).
Auto Fan Off: Enable or disable the auto fan off
feature.
Run Hours: Adjust fan run time before the fan
automatically shuts off.
• Power Supply Settings
POWER SUPPLY SETTINGS
POWER SUPPLY SETTINGS
POWER SUPPLY TYPE: JC062
POWER SUPPLY TYPE: JC062
POWER SUPPLY OPERATING
POWER SUPPLY OPERATING
VOLTAGE
VOLTAGE
PASS 1:
PASS 1:
3.0
3.0
VDC
VDC
12.0 KV
12.0 KV
PASS 2:
PASS 2:
3.0
3.0
VDC
VDC
12.0 KV
12.0 KV
PASS 3:
PASS 3:
3.0
3.0
VDC
VDC
12.0 KV
12.0 KV
POWER SUPPLY INITIAL RESET
POWER SUPPLY INITIAL RESET
ATTEMPTS BEFORE ALARM
ATTEMPTS BEFORE ALARM
15
15
Power Supply Operating Voltage: Adjustable output
signal power to power supplies and the corresponding
kV output. This is adjustable only if provided with JC062
power supplies.
Power Supply Initial Reset Attempts before Alarm:
(If provided with JC062 power supplies) Adjustable
power supply reset attempts upon a fault before
entering an alarm for the power supplies.
Power Supply Alarm Reset Delay: (If provided with
JC062 power supplies) Adjustable time delay after a
power supply alarm has occurred in which the system
attempts to retry the power supplies.
• General Wash Settings
GENERAL WASH SETTINGS
SETTINGS
WASH SCHEDULE
AND TIMING
Navigating to the Wash Schedule and Timing screen will
allow the user to adjust the auto wash settings and the
timing sequences within the wash cycle. Navigating to
the Test Wash Setup screen will allow the user to adjust
test wash timing sequences and start a test wash.
POWER SUPPLY ALARM RESET
POWER SUPPLY ALARM RESET
DELAY:
DELAY:
10
10
MINUTES
MINUTES
TEST WASH