Technical Data - Tekmar Eight Stage Boiler Control 258 Data Brochure

Advertisement

Technical Data

Technical Specifications
Dimension (h x w x d)
Weight
Ambient
Power supply
Relay capacity
Sensors
Control accuracy (temp.)
Control Processing
This electronic control does not exceed the Class B limits for radio noise emissions from digital apparatus as set out in the Radio Interference Regulations of the
Canadian Department of Communications. Le présent numérique n'émete pas de bruits radioeléctriques dépassant les limites applicables aux appareils numériques de
Classe B prescrites dans le réglement sur le brouillace radioeléctrique édicté par le Ministére des Communications du Canada.
Features
18 Indicator lights
Comb. air damper output
Pump output
Stage 1 to 7 output
Stage 8
Test button
Error message display
Setback timer/clock
Memory backup
Battery backup
Dial & Switch Settings
Heating Curve
Minimum
Boiler Differential
Stage 1 to 8 switches
Rotate switch
Fixed lead switch
Fixed last switch
Lo/Hi fire switch
Timer switch
Heat Demand switch
Setpoint/Reset switch
Keypad Programming
Occupied room temperature
UnOccupied room temperature
Occupied Setpoint temperature
UnOccupied Setpoint temperature — 70 to 248°F (21 to 120°C)
Override temperature
Setback schedules
Display Readouts
Desired Occ.temperature
Desired UnOcc. temperature
Desired Occ. Setpoint temp.
Desired UnOcc. Setpoint temp.
Override temperature
Actual Supply temperature
Outdoor temperature
Target supply temperature
Boiler accumulated running times — 0 to 999,999 hrs. for each stage
Setback schedules
Time of Day/Day of Week
— 6-5/8" x 7-9/16" x 2-13/16" (170 x 193 x 72mm)
— 2.9 lbs (1.3 Kg)
— 30 to 120°F (0 to 50°C), < 95% RH non-condensing
— 24Vac ± 10%, 60Hz, 5VA class II
— For alternate power supplies (50Hz or 24Vdc), contact the factory
— 9 x SPST, 24Vac, 10 Amps – 1 x SPDT, 24Vac, 8 Amps
— Outdoor Sensor 070, Sensor 071; Accurate with up to 500 feet (150m) 18AWG cable
— ± 1°F (± 0.5°C)
— PID algorithm
— Power, Heat Demand, Setpoint, WWSD, Minimum, Comb. air, Pump, Actual Supply, Target Supply
Stage 1, Stage 2, Stage 3, Stage 4, Stage 5, Stage 6, Stage 7, Stage 8, Test
— Isolated SPST relay contacts close before first boiler is fired (60 sec.)
— Isolated SPST relay contacts close when heating or setpoint is required
— Isolated SPST relay contacts close to operate each stage
— Isolated SPDT relay contacts. N.O. contacts close to operate Stage 8
— Initiates and controls pre-programmed test run
— Sensor faults are indicated by flashing light code
— Programmable
— Retains programmed information and boiler run times when powered down for up to 10 years
— Maintains clock operation for 24hrs when powered down
— 0.4 to 3.6
— Off, 80 to 170°F (Off, 27 to 77°C)
— 2 to 42°F (1 to 23°C)
— To switch each Stage off or into operating mode
— To allow boilers to rotate firing sequence based on hours of use (re-ranks after 48 hrs of use)
— Configures Stage 1 to be first/on first/off regardless of hours of use
— Configures last Stage to be last on first off regardless of hours of use
— Configures Stages to fire and rotate as pairs
— Setback input from internal timer or external source
— External 24Vac signal or permanent internal signal
— Control operates in reset or setpoint mode
— 35 to 105°F (2 to 41°C)
— 35 to 105°F (2 to 41°C)
— 70 to 248°F (21 to 120°C)
— Setpoint or Room temperature ranges depending on mode
— 6 pre-programmed, 1 programmable — 7 day, 2 events per day
— 35 to 105°F (2 to 41°C)
— 35 to 105°F (2 to 41°C)
— 70 to 248°F (21 to 120°C)
— 70 to 248°F (21 to 120°C)
— Setpoint or Room temperature ranges depending on mode
— -67 to 293°F (-55 to 145°C)
— -67 to 293°F (-55 to 145°C)
— 35 to 248°F (2 to 120°C)
— 6 pre-programmed, 1 programmable — 7 day, 2 events per day
— 12 hr., 7 day clock
19