Error Code - York R410A User Manual

Hide thumbs Also See for R410A:

Advertisement

Error code

Diagnosis for models
YIFFXC025BAEFA YIFFXC030BAEFA YIFFXC036BAEFA YIFFXC036BANFA YIFFXC040BANFA
LED flash
Wired
times of signal
controller
receiver board
display
1
E1
2
E2
5
E5
9
E8
10
E0
14
FC
YIFFXC040BAEFB
LED flash
Wired
times of signal
controller
receiver board
display
0
1
01
0
2
02
0
4
04
0
7
07
0
8
/
0
12
0C
0
13
0D
0
16
10
Note:
1. The outdoor failure can also be indicated by the indoor unit, the checking method as follows: LED4 flash times stands
for tens digit, and LED3 flash times stands for units digit, use this bidigitate figure minus 20, then will get the outdoor
error code. For example, if the outdoor error code is 15, LED4 will flash 3 times firstly, two seconds later, LED3 will flash
5 times, and four seconds later the process will repeat again.
2. LED4 is a yellow one on the indoor PCB, LED3 is a green one.
3. To get much more details about the out door unit failure, please refer to the outdoor unit trouble shooting list.
Contents of Malfunction
Malfunction of indoor unit ambient
temperature sensor
Malfunction of indoor unit piping
temperature sensor
Compressor overcurrent / phase
sequence wrong
Abnormal communication between
wired controller and indoor unit
Malfunction of drain system
Indoor coil temperature too high in
cooling mode
Contents of Malfunction
Malfunction of indoor unit ambient
temperature sensor
Malfunction of indoor unit ambient
temperature sensor
EEPROM wrong of indoor PCB
Abnormal communication between
indoor and outdoor units.
Abnormal communication between
wired controller and indoor unit
Malfunction of drain system
Zero cross sigal wrong
Indoor abnormal mode operation
Possible reasons
Sensor disconected,or broken, or at wrong position,
or short circuit
Sensor disconected, or broken, or at wrong position,
or short circuit
Overcurrent after compressor running or power suppl
phase sequence wrong before compressor running.It
occurs 3 times in 1 hour, comfirm the failure, the former
twice will not alarm.
Wrong connection or wired controller broken, or PCB
faulty
Pump motor disconnected or at wrong position,or
the float switch disconnected, or at wrong position,
or the short circuit bridge disconne ted
Refrigerant leakage or indoor coil sensor falling off
Possible reasons
Sensor disconected,or broken, or at wrong position,
or short circuit
Sensor disconected,or broken, or at wrong position,
or short circuit
EEPROM chip disconected or broken or wrong
programmed, or PCB broken
Wrong connection,or the wires be disconected or wrong
adress setting of indoor unit or faulty power supply or
faulty PCB or slave unit malfunction in MAXI system.
Wrong connection or wired controller broken, or PCB
faulty
Pump motor disconnected or at wrong position,or
the float switch disconnected, or at wrong position,
or the short circuit bridge disconne ted
Zero cross sigal detected wrong
Different from outdoor unit mode
11