Zennio MAXinBOX 8 Plus Technical Documentation

Zennio MAXinBOX 8 Plus Technical Documentation

Multi-function actuator with 8 outputs 16a

Advertisement

Quick Links

Multi-function actuator with 8 outputs 16A
ZIO-MB8P
FEATURES
 2 different configurable blocks:
Shutter channels (up to 4).
Individual outputs (up to 8).
2-pipe fan coil control (up to 2 units).
 Manual output operation with push button and LED
status indicator.
 Suitable for capacitive loads, maximum 140 µF.
 Logical functions included.
 Output timing facilities.
 Total data saving on power failure
 Size 67 x 90 x 80 mm (4.5 DIN units).
 DIN rail unit assembly (EN 50022), with snap fit clamp.
 No external power supply required other than the bus.
 KNX BCU integrated.
 Possibility to connect different phases in adjoining
outputs.
 CE directives compliant.
1. Upper
2. Lower output
outputs
screws
5.Programming/Test
button
GENERAL SYSTEM SPECIFICATIONS
CONCEPT
Type of device
Voltage (typical)
Voltage range
KNX supply
Maximum
consumption
Bus connection
External power supply
Ambient temperature
Storage temperature
Ambient humidity
Storage humidity (relative)
Complementary characteristics
Safety class
Operation type
Device action type
Electrical solicitations period
Type of protection
Assembly
KNX bus failure response
Response when restarting KNX bus
Operation indication
Weight
PCB CTI index
Enclosure
(1)
Maximum consumption in the worst case scenario (KNX Fan-In model)
© Zennio Avance y Tecnología S.L.
3.Programming/Test
LED
6.Output control
7.Output status LED
button
Voltage
29VDC (typical)
(1)
24VDC
Edition 1
6
Programming/test button: short button press to set programming
mode. If this button is held while plugging the device into the KNX
bus, it goes into safe mode. If this button is held more than 3
seconds, the device goes into manual mode (test mode)
LED: programming mode indicator (red). When the device goes into
4.KNX
safe mode, it blinks (red) every half second. The manual mode is
connector
indicated by the colour green. During start up (after reset or power
failure) and if the device is not in safe mode, LED blinks in blue for a
few seconds
indicator
DESCRIPTION
Electric operation control device
29V DC SELV
21...31V DC
mA
5.8
10
Typical bus connector TP1, 0,50 mm² section
No
from 0ºC to +55ºC
from -20ºC to +70ºC
5 to 95% RH (no condensation)
5 to 95% RH (no condensation)
Class B
II
Continuous operation
Type 1
Long
IP20, clean environment
Independent control assembly device to be mounted inside of electrical panels
with DIN rail (EN 50022).
Data saving and relays open if channel configured as shutter.
Data recovering and output status change according to programming when
recovering.
Programming LED indicates programming mode (red) and test mode (green).
Output status LED indicators reflect current output state.
290 g.
175 V
PC FR V0 halogen free
Further information
MAXinBOX 8 Plus
Technical Documentation
1
3
2
Figure 1. MAXinBOX 8 Plus
www.zennio.com
7
5
4
mW
168.2
240