Download Print this page

Eaton P5-125/E Instruction Leaflet page 2

Advertisement

P5-125(160)(250)(315)/EA/SVB
P5-125(160)(250)(315)/EA/SVB-SW
P5-160/EA/SVB-SW-SCM
P5-125(160)(250)(315)/EA/SVB-SW/HI10
P5-125(160)(250)(315)/EA/SVB/HI10
UL60947-4-1, UL508
Temperature rating of wire 75°C
These devices are suitable for use on circuits capable of delivering
not more than 10 kA rms symmetrical amperes 600 V ac max.
when protected by Type RK1 fuses.
Use copper wire only
Torque value for field wiring terminals: Typ
HI10
PH1
A = 5
B = 6
HI...P5
2
0.5 - 2.5 mm
2
0.5 - 2.5 mm
0.8 Nm (7.0 lb-in)
2/2
Eaton Industries GmbH, Hein-Moeller-Straße 7-11, 53115 Bonn, Germany
© 2011 by Eaton Industries GmbH,
Eaton.eu/documentation
lb-in
Nm
P5-125... 125
14
P5-160... 125
14
P5-250... 140
16
P5-315... 140
16
(3/4 x )
⌀ 6 m
(⌀ 0.24")
⌀ 13 - 17 mm
(⌀ 0.51 - 0.67")
P5-125(160)/EA/SVB...
1 x 70 mm
2 x 25 mm
1 x 95 mm
2 x 35 mm
1 x 13 x 3
2 x 13 x 1.5
14 Nm (125 lb-in)
P5-125(160)(250)(315)/EA/SVB/N
P5-125(160)(250)(315)/EA/SVB-SW/N
P5-160/EA/SVB-SW/N-SCM
P5-125/...
P5-160/...
P5-250/...
P5-315/...
IEC60947-3 / EN60947-3 / VDE0660-107
Max Fuse Rating: Typ
P5-125...
P5-160...
P5-250...
P5-315...
m
P5-250(315)/EA/SVB...
2
1 x 120 mm
2
2 x 50 mm
2
1 x 185 mm
2
2 x 70 mm
1 x 20 x 5
2 x 20 x 3
16 Nm (140 lb-in)
Emergency On Call Service: Local representative (Eaton.eu/aftersales) or +49 (0) 180 5 223822 (de, en)
Eaton.com/recycling
All Rights Reserved
A
B
Fuse characteristic
Numb Fuses Current (A)
gG
1
gG
1
gG
1
gG
1
d
d = 3 - 9 mm
(d = 0.12 - 0.35")
≦ 3 x
M5
PH2
2
2
2
2
V0P K022 M
125
160
250
315
PH2
04/18 IL03802010Z

Advertisement

loading

This manual is also suitable for: