Installing An Ecc800 - Huawei FusionModule2000 Installation Manual

Smart modular data center 2000 mmhigh cabinets, dual-row aisle containment, 208 v
Hide thumbs Also See for FusionModule2000:
Table of Contents

Advertisement

FusionModule2000 Smart Modular Data Center
Installation Guide (2000 mm High Cabinets, Dual-Row
Aisle Containment, 208 V)
Figure 8-8 Installing a LAN switch
Step 3 Connect the LAN switch power cable to the PDU2000.
----End
Follow-up Procedure
If a 24-port LAN switch is configured, two power modules need to be installed for the LAN
switch onsite. Insert the power modules into the power slots of the 24-port LAN switch, and
tighten the captive screws on the power module panel.
Figure 8-9 Installing the power modules for a 24-port LAN switch

8.5 Installing an ECC800

Procedure
Step 1 Determine the mounting holes for an ECC800 based on the network cabinet device layout,
adjust the guide rails, and install floating nuts.
Step 2 Place the ECC800 in the network cabinet with caution.
Issue 01 (2017-07-30)
The positions of power cable ports vary depending on the LAN switch models. Connect the power cable
based on the actual power port of the LAN switch.