Troubleshooting Guide
Error
Error Type
No.
21*
Master
211
Slave1
Comp PCB Assy IPM Fault
212
occur
Slave2
213
Slave3
214
n Error diagnosis and countermeasure flow chart
Are there any power wire
connections normal?
Yes
Are the resistance
Between each phase and
insulation resistance of Inverter
compressor normal?
Yes
Is compressor
Wire connection
condition normal?
Yes
Is DC_Link Wire connection
condition normal?
Yes
Is Comp IPM heat sink's
joining condition normal?
Yes
Is Comp PCB assembly
normal?
Yes
Recheck power and installation condition
Copyright ©2013 LG Electronics. Inc. All right reserved.
Only for training and service purposes
Error Point
IPM self protection circuit
activation
(Overcurrent/IPM overheat-
ing/Vcc low voltage)
No
1. Check R/S/T/N Wiring Condition
→ Rewire them if abnormality found
1. Check resistance between each terminal of compressor
(U-V:0.26 ±7%, V-W:0.26 ±7%,W-U:0.26 ±7% (25℃))
No
2. Check insulation resistance between compressor
terminal and pipe (over 50M )
→ Replace compressor if abnormality found
1.Check Comp PCB assembly U,V,W connector
connection condition
No
2. Check wire disconnection and wiring
3. Check compressor terminal connection condition
(bad contact)
→ Reassemble if abnormality found
1.Check Comp PCB assembly P,N connector
connection condition
2.Check Converter PCB assembly P,N connector
No
connection condition
3. Check wire disconnection and wiring
→ Reassemble if abnormality found
1.Check Comp PCB assembly Comp IPM heat sink
No
joining condition
→ Reassemble if abnormality found
Check Comp PCB assembly IPM normality.
No
→ Replace Comp PCB assembly
if abnormality found.
- 88 -
Main Reasons
1.Over current detection at Inverter compres-
sor(U,V,W)
2.Compressor damaged (insulation dam-
aged/Motor damaged)
3.IPM overheating
(Heat sink disassembled)
4.Inverter compressor terminal disconnected
or loose
5.Inverter PCB assembly damaged
6.ODU input current low
LGE Internal Use Only