2.1.2 Oil return control on heating mode
Outdoor Unit
Component
Inv Compressor
FAN
Main EEV
Subcooling EEV
4way valve
Indoor Unit
Component
Fan
Thermo on unit EEV
Thermo off unit EEV
n Oil return operation time : 3 min for running step
n Starting condition:same as cooling mode
n Oil return process ends if compressor protection control starts
Copyright ©2013 LG Electronics. Inc. All right reserved.
Only for training and service purposes
Starting
30Hz
Normal control
Upper : Min. pulse
Upper : Min. pulse
Low : Max. pulse
Low : Max. pulse
Min. pulse
ON
Starting
Normal control
Normal control
80~130 pulse
- 21 -
Running
Setting Value
Normal control
Normal control
Upper : Normal control
Low : Normal control
20 pulse
OFF
Running
OFF
Normal control
400~800 pulse
Normal control
400~800 pulse
80~130 pulse
LGE Internal Use Only
Function
Ending
40Hz
80 pulse
ON
Ending