Troubleshooting Guide
Error No.
Error Type
194*
Master
1941
Outdoor unit Fan PCB
Slave1
1942
heatsink temperature
Slave2
sensor error
1943
Slave3
1944
n Error diagnosis and countermeasure flow chart
Is temperature sensor
connector connections
are normal?
Yes
Is the value of temperature
sensor resistance normal?*
Yes
Replace outdoor unit PCB
* Sensor resistance 100 kΩ over (open) or 100 Ω below (short) will generate error
Note: Temperate sensor resistance vary with temperature, So compare temperature sensor resistance value
according to outdoor unit temperature by referring below table (±5% tolerance)
Air temperature sensor: 10°C = 20.7kΩ : 25°C = 10kΩ : 50°C= 3.4kΩ
Pipe temperature sensor: 10°C = 10kΩ : 25°C = 5kΩ : 50°C= 1.8kΩ
Copyright ©2013 LG Electronics. Inc. All right reserved.
Only for training and service purposes
Error Point
Outdoor unit Fan PCB
heatsink temperature
sensor error
No
Check and correct connection
No
Replace sensor
- 136 -
Main Reasons
1. Defective temperature sensor connection
2. Defective temperature sensor (Open / Short)
3. Defective outdoor unit PCB
LGE Internal Use Only