Troubleshooting Guide
Error
Error Type
No.
40*
Master
401
Slave1
Inverter compressor CT
402
sensor error
Slave2
403
Slave3
404
n Error Diagnosis and Countermeasure Flow Chart
Are there any power wire
connections normal?
Yes
Is input voltage normal?
Yes
Is Comp PCB assembly normal?
Yes
Recheck power and installation condition
* Measuring input voltage
Copyright ©2013 LG Electronics. Inc. All right reserved.
Only for training and service purposes
Error Point
Micom input voltage isn't
within 2.5V ±0.3V at initial
state of power supply
1. Check R/S/T/N wiring conditions
No
2. Check Noise filter wiring conditions
→ Rewire them if abnormality found.
Check
R~S/S~T/T~R phase voltage is 380V±10%
No
R~N/S~N/T~N phase voltage is 220V±10%
→ Check connection condition and wiring if power is
abnormal
No
Replace Comp PCB assembly
* Comp PCB assembly
- 104 -
Main Reasons
1. Input voltage abnormal (R-N)
2. ODU Comp PCB damage
(CT sensing part)