Error Messages

The control was unable to read a piece of information from its EEPROM. This error can be caused
by a noisy power source. The control will load the factory defaults and stop operation until all the
settings are verified.
The control is no longer able to read the outdoor sensor due to a short circuit. In this case the con-
trol assumes an outdoor temperature of 32°F (0°C) and continues operation. Locate and repair the
problem as described in the Data Brochure D 070e. To clear the error message from the control after
the sensor has been repaired, press the Item button.
The control is no longer able to read the outdoor sensor due to an open circuit. In this case the
control assumes an outdoor temperature of 32°F (0°C) and continues operation. Locate and repair
the problem as described in the Data Brochure D 070e. To clear the error message from the control
after the sensor has been repaired, press the Item button.
The control is no longer able to read the mixing supply sensor due to a short circuit. In this case the
control will operate the mixing valve at a fixed output as long as there is a mixing demand. Locate
and repair the problem as described in the Data Brochure D 070e. To clear the error message from
the control after the sensor has been repaired, press the Item button.
The control is no longer able to read the mixing supply sensor due to a short circuit. In this case the
control will operate the mixing valve at a fixed output as long as there is a mixing demand. Locate
and repair the problem as described in the Data Brochure D 070e. To clear the error message from
the control after the sensor has been repaired, press the Item button.
The control is no longer able to read the boiler sensor due to a short circuit. If the BOIL MIN adjust-
ment is higher than 100°F (38°C), the control closes the Boiler contact when the mixing valve starts
to operate. The boiler temperature is then limited by the operating aquastat. If the BOIL MIN adjust-
ment is lower than 100°F (38°C), the control does not operate the Boiler contact. Locate and repair
the problem as described in the Data Brochure D 070e. To clear the error message from the control
after the sensor has been repaired, press the Item button.
The control is no longer able to read the boiler sensor due to an open circuit. If the BOIL MIN adjust-
ment is higher than 100°F (38°C), the control closes the Boiler contact when the mixing valve starts
to operate. The boiler temperature is then limited by the operating aquastat. If the BOIL MIN adjust-
ment is lower than 100°F (38°C), the control does not operate the Boiler contact. Locate and repair
the problem as described in the Data Brochure D 070e. If the boiler sensor is deliberately removed,
the control must be powered down, and then powered back up. To clear the error message from the
control after the sensor has been repaired, press the Item button.
The control is no longer able to read the indoor sensor due to a short circuit. The control will con-
tinue to operate as if there was nothing connected to the indoor sensor input. Locate and repair the
problem as described in the Data Brochure D 070e. To clear the error message from the control after
the sensor has been repaired, press the Item button.
The control is no longer able to read the indoor sensor due to an open circuit. The control will con-
tinue to operate as if there was nothing connected to the indoor sensor input. Locate and repair the
problem as described in the Data Brochure D 070e. If the indoor sensor is deliberately removed,
the control must be powered down, and then powered back up. To clear the error message from the
control after the sensor has been repaired, press the Item button.