Adjust Menu - Kanmor 360e Data Brochure

Mixing control
Table of Contents

Advertisement

Adjust Menu (1 of 2)
Display
Terminal Unit
Motor Speed
© 2003
D 360e - 06/03
The desired room air temperature during an
occupied (Day) period.
B2
(OUTDR DSGN ≠ OFF)
The desired room air temperature during an
unoccupied (Night) period.
B2
(OUTDR DSGN ≠ OFF)
Mixing setpoint temperature.
B2
(OUTDR DSGN = OFF)
The design outdoor air temperature used in the
heat loss calculation for the heating system. For
B2
setpoint operation, set the OUTDR DSGN to OFF
The type of terminal units that are being used
B2
in the heating system.
(OUTDR DSGN ≠ OFF)
The design indoor air temperature used in the
heat loss calculation for the heating system.
B3
(OUTDR DSGN ≠ OFF)
The design supply water temperature used in
the heat loss calculation for the heating system.
B3
(OUTDR DSGN ≠ OFF)
The maximum supply water temperature for the
mixing system
B3
(OUTDR DSGN ≠ OFF)
The time that the actuating motor requires to
A
operate from fully closed to fully open.
The minimum supply temperature for the
B3
mixing system.
(OUTDR DSGN ≠ OFF)
The minimum temperature allowed for the boiler
C1
target temperature.
(Boiler sensor is present)
Description
16 of 20
Actual
Range
Setting
35 to 100°F
(2 to 38°C)
35 to 100°F
(2 to 38°C)
60 to 200°F
(16 to 93°C)
-60 to 32°, OFF
(-51 to 0°C, OFF)
1 (High Mass Radiant
2 (Low Mass Radiant
3 (Fancoil)
4 (Fin-tube Convector
5 (Radiator)
6 (Baseboard)
35 to 100°F
(2 to 38°C)
70 to 220°F
(21 to 104°C)
80 to 210°F
(27 to 99°C)
30 to 230 seconds
(1 sec. increments)
OFF, 35 to 150°F
(OFF, 2 to 65°C)
OFF, 80 to 180°F
(OFF, 27 to 82°C)