Testing And Troubleshooting - Kanmor 360e Data Brochure

Mixing control
Table of Contents

Advertisement

Adjust Menu (2 of 2)
Display
Testing the Control
The Mixing Control 360e has a built-in test routine which is used to test the main control
functions. The 360e continually monitors the sensors, and displays an error message
whenever a fault is found. See the following pages for a list of the 360e's error mes-
sages and possible causes. When the Test button is pressed, the test light is turned
on. The individual outputs and relays are tested in the following test sequence.
TEST SEQUENCE
Each step in the test sequence lasts 10 seconds.
During the test routine, the test sequence may be paused by pressing the Test button. Only if there is a mixing demand can the
control be paused in a step. If the Test button is not pressed again for 5 minutes while the test sequence is paused, the control
exits the entire test routine. If the test sequence is paused, the Test button can be pressed again to advance to the next step.
This can also be used to rapidly advance through the test sequence. To reach the desired step, repeatedly press and release
the Test button until the appropriate device and segment in the display turn on.
Step 1
- The mixing valve is run fully open.
Step 2
- The mixing valve is run fully closed, and then the system pump (Sys Pmp) is turned on.
Step 3
- The Boiler contact is turned on for 10 seconds. After 10 seconds, the Boiler and Sys Pmp contacts are shut off.
Step 4
- After the test sequence is completed, the control resumes its normal operation.
The differential that the control is to use when
it is operating the boiler.
C2
(Boiler Sensor DIP switch = Supply AND
Boiler sensor is present)
The system's warm weather shut down during
B3
the occupied (Day) period.
The system's warm weather shut down during
B3
the unoccupied (Night) period.
The units of measure that all of the temperatures
are to be displayed in the control.
This item exits the ADJUST menu by pressing
either the
Description
or
button.
17 of 20
Actual
Range
Setting
Ad, 2 to 42°F
(Ad, -17 to 6°C)
35 to 100°F, OFF
(2 to 38°C, OFF)
35 to 100°F, OFF
(2 to 38°C, OFF)
°F, °C
Test
© 2003
D 360e - 06/03