Kanmor 360e Data Brochure page 11

Mixing control
Table of Contents

Advertisement

Output Connections
System Pump Contact (Sys Pmp)
The Sys Pmp output terminal (5) on the 360e is a powered output. When the
relay in the 360e closes, 120 V (ac) is provided to the Sys Pmp terminal (5) from
the Power L terminal (3). To operate the system pump, connect one side of the
system pump circuit to terminal (5), and the second side of the pump circuit to the
neutral (N ) terminal 6.
Mixing Valve Actuator
Terminals 9, 10 and 11 are isolated outputs from the control.
Connect one side of the actuator power to the Pwr Mix terminal
(9) on the control. The output relay Opn (10) is then connected
to the open terminal of the actuator and the output relay Cls (11)
is connected to the close terminal of the actuator. Connect the
second side of the actuator power to the common terminal of
the actuator.
Boiler Contact
The Boiler terminals (7 and 8) are an isolated output in the 360e. There is no
power available on these terminals from the control. These terminals are to
be used as a switch to either make or break the boiler circuit. When the 360e
requires the boiler to fire, it closes the contact between terminals 7 and 8.
Sensor and Unpowered Input Connections
Do not apply power to these terminals as this will damage the control.
Outdoor Sensor
Connect the two wires from the Outdoor Sensor 070e to the Com and Out termi-
nals (16 and 17). The outdoor sensor is used by the 360e to measure the outdoor
air temperature
Boiler Sensor
Connect the two wires from the Boiler Sensor 071e to the Com
and Boil terminals (13 and 14). The boiler sensor is used by the
360e to measure boiler temperature.
Mixing Sensor
Connect the two wires from the Mixing Sensor 071e to the Com
and Mix terminals (13 and 15). The mixing sensor is used by
the 360e to measure the supply water temperateure after the
mixing valve. Normally the sensor is attached to the pipe down-
stream of the system pump.
L
11 of 20
230 V (ac)
L
N
N
Boiler Supply
Sensor
or
Boiler Return
Sensor
Mix Supply
© 2003
D 360e - 06/03
Sensor
System
Pump

Advertisement