Installation; Electrical Connections - Kanmor 360e Data Brochure

Mixing control
Table of Contents

Advertisement

The control can be mounted
on a standard DIN rail. This
will be a popular option for
those who prefer to mount
the control inside a larger
electrical panel.
STEP THREE
All electrical wiring terminates in the control base wiring chamber. The base has standard 7/8" (22 mm) knockouts which accept
common wiring hardware and conduit fittings. Before removing the knockouts, check the wiring diagram and select those sec-
tions of the chamber with common voltages. Do not allow the wiring to cross between sections, as the wires will interfere with
safety dividers, which should be installed at a later time.
Power must not be applied to any of the wires during the rough-in wiring stage.
• All wires are to be stripped to a length of 3/8" (9 mm) to ensure proper connection to the control.
• Install the Outdoor Sensor 070e according to the installation instructions in the Data Brochure D 070e and run the
wiring back to the control.
• Install the Mixing Sensor 071e according to the installation instructions in the Data Brochure D 070e and run the wiring
back to the control.
• If a Boiler Sensor 071e is used, install the sensor according to the installation instructions in the Data Brochure D 070e
and run the wiring back to the control.
• If an Indoor Sensor 076e is used, install the sensor according to the installation instructions in the Data Brochure D
070e and run the wiring back to the control.
• Run wire from other system components (pumps, boilers, etc.) to the control.
• Run wires from the 230 V (ac) power to the control. Use a clean power source with a 15 A circuit to ensure proper
operation. Multi-strand 16 AWG wire is recommended for all 230 V (ac) wiring due to its superior flexibility and ease of
installation into the terminals.
STEP FOUR
The installer should test to confirm that no voltage is present at any of the wires. Push the control into the base and slide it down
until it snaps firmly into place.
Powered Input Connections
230 V (ac) Power
Connect the 230 V (ac) power supply to the Power L and Power N terminals (3
and 4). This connection provides power to the microprocessor and display of the
control. As well, this connection provides power to the Sys Pmp terminal (5) from
the Power L terminal (3).
Mixing Demand
To generate a mixing demand, a voltage between 24 V (ac) and 230 V (ac) must
be applied across the Mixing Demand terminals (1 and 2).
© 2003
D 360e - 06/03
The wiring can enter the bottom
or the back of the enclosure.
Knock-outs provided in the base
allow the wiring to be run in con-
duit up to the enclosure. The
base also has holes that line up
with the mounting holes of most
common electrical boxes.
ROUGH-IN WIRING
ELECTRICAL CONNECTIONS TO THE CONTROL
10 of 20
230 V (ac)
24 to 230 V (ac)