Activity C | Electrical Connection
Models 18 - 36 Kilowatts are supplied with a 4 to 6 prong terminal block (depending on model) marked
(circuit breaker A - L1 L2) (circuit breaker B - L1 L2) (circuit breaker C - L1 L2) & (circuit breaker D - L1 L2).
Each one of the circuit sets must be connected to an in-dependent double pole 40 amp breaker.
Circuit A – L1-L1 goes to one 40 amp double pole breaker, Circuit B – L1-L2 goes to
another 40 amp double pole breaker and so on. (See below image.)
You must ensure the set of wires from each leg are not crossed at the breakers otherwise the unit will
not function as designed. In order to make sure the wiring is connected correctly perform the following
test located on the following page.