Bentone MB-ZRDLE 420 Installation And Maintenance Manual
Bentone MB-ZRDLE 420 Installation And Maintenance Manual

Bentone MB-ZRDLE 420 Installation And Maintenance Manual

Advertisement

Quick Links

Translation of the original instructions.
Keep for future use.
Read carefully before use.
178 141 82-2 CR00783 2024-07-02
Installation and Maintenance Manual
BG 650-2
LME22.232C2E
MB-ZRDLE 420

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the MB-ZRDLE 420 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Bentone MB-ZRDLE 420

  • Page 1 Installation and Maintenance Manual BG 650-2 LME22.232C2E MB-ZRDLE 420 Translation of the original instructions. Keep for future use. Read carefully before use. 178 141 82-2 CR00783 2024-07-02...
  • Page 2 1~230V 1,0A 50Hz IP 20 Motor supply MADE IN SWEDEN BY 1. Manualer på övriga språk 1. Manuals in other languages 1. Manualer på andre sprog 2. www.bentone.com\nedladdning eller 2. www.bentone.com\download 2. www.bentone.com\download eller scanna QR-koden. or scan QR-code. scan QR-koden.
  • Page 3: Table Of Contents

    BENTONE Table of contents General Information ............5 Settings ................23 Delivery inspection................ 5 Setting the combustion assembly ........... 23 Safety ....................5 Startup ................... 23 What to do if you smell gas ............6 Control of combustion .............. 23 6.4 Setting the air pressure switch ..........24 Technical data ...............7...
  • Page 5: General Information

    BENTONE General Information The burner may only be used for its intended purpose in accordance with the product’s technical data. We reserve the right to make design changes and cannot be held liable for any misprints or typographical errors. Modifying the design or using accessories or components that have not been approved by CTC in writing is strictly prohibited.
  • Page 6: What To Do If You Smell Gas

    BENTONE • Care must be taken by the installer to ensure that no electrical cables or fuel lines are pinched or otherwise damaged during installation or service. Sharp edges can occur on, for example: flame tube, fan wheel and air •...
  • Page 7: Technical Data

    BENTONE Technical data The burner is intended for: • Operation in installations according to EN 303 and EN 676. Fuels: • Natural gas H, E, L, LL. • LPG, Butane and Propane. Dimensions BG 650-2 E F *G Flame tube...
  • Page 8: Gas Categories, Approved Gases

    BENTONE 2.1.1 Measurements for connection to the boiler (ø210) ø255-290 Ø (170)190 Capacity range Capacity Gas quantity at min. Gas quantity at max. Max. connection Nominal power power pressure connection mbar pressure mbar 650 / 650i G20 200 - 1125 21.2 119.0...
  • Page 9: Technical Specification

    BENTONE Technical specification BG 650-2 Main supply, Operation 230V, 1~, 0.8A, 50Hz, IP20 1) 2) Main supply, Motor 230/400V, 5.9/3.4A Max fuse rating, Motor 6.3A Max fuse rating, Operating -class 2 - G20, G25, G31, 3 - G30 Sound power (dBA) L 91dBA Max operating current, see data plate.
  • Page 10: Components

    BENTONE Components Flame tube Ionisation electrode Indication lamp, Stage 2 Fixing flange Motor Power switch I-II Guides Connection, gas Indication lamp, Stage 1 Fan wheel Transformer Power switch 0-I Gas pressure switch, min Air damper Contactor + Overload protection Brake plate...
  • Page 11 BENTONE...
  • Page 12: Skeleton Diagrams

    BENTONE Skeleton diagrams Ball valve Filter Pressure regulator Pressure gauge with shut-off cock Gas pressure switch, min Gas pressure switch, max Main valve, 2 -stage. In modulaing operation, this valve is equipped with controls for variable opening. Safety valve Leakage control...
  • Page 13: Electric Equipment

    BENTONE Electric equipment Safety system The safety system (safety switch for hatches, doors, water level, pressure, temperature and other safety devices) must be installed in the safety circuit in accordance with current regulations for the system. The cables of the safety system must be separated so that the outgoing signal is not placed in the same cable as the incoming signal.
  • Page 14: Function

    BENTONE 3.2.1 Components Burner control Operating switch, Stage 2 Connection terminal board Ionization electrode Control thermostat Earth terminal Operating fuse Temperature limiter Plug-in contact, burner Operation fuse Safetyswitch for hinged door Plug-in contact, boiler Lamp, Low capacity Control thermostat, Stage 2...
  • Page 15: Control Program At Faults; Fault Mode Indicator Lme

    BENTONE Control program at faults; fault mode indicator LME ..3.4.1 Colour codes Table colour codes for multi-coloured signal light (LED) Status Colour codes Colours ○………………… Waiting period «tw», other waiting periods ●○●○●○●○●○● Ignition phase, ignition controlled Blinking yellow □…………………...
  • Page 16 BENTONE 3.4.5 Alarm code table Red blinking code on Possible causes signal lamp (LED) Blinking 2 x No flame creation at End of “TSA” – defective or fouled flame monitoring. •• – defective or fouled fuel valves. – poor burner setting.
  • Page 17: Installation

    BENTONE Installation General instructions Installation must be carried out in accordance with current regulations and instructions. The supplier/installer of the facility is obliged to familiarize himself with all regulations so that the installation meets the requirements of the local authorities.
  • Page 18: Handling And Lifting Instruction

    BENTONE Handling and lifting instruction The lifting aid are available as accessories.
  • Page 19: Mounting

    BENTONE Mounting Mount the burner to the boiler using 4 bolts (if new fixing holes need to be drilled, use the fixing flange as a template). Separate the fixing flange from the fan housing as follows: Remove cover of fan housing (A), disconnect ignition and ionizing cables and the control arm (B) from nozzle assembly.
  • Page 20: Gas Nozzle

    BENTONE Gas nozzle Check that the ignition electrodes are correctly set before mounting on the boiler. Natural gas Propane Biogas (UV detector)
  • Page 21: Aerating

    BENTONE De-aerating De-aerating the gas line by closing the tap to the gas connection and unscrewing the screw on the measuring nipple for the connection pressure. Connect a plastic hose, open the tap and drain the gas in a safe place. When the de-aerating is completed, be sure to refit the screw on the measuring nipple.
  • Page 22: Calculation Of Gas Flow

    BENTONE Calculation of gas flow Formula symbol Description Example values Standard gas volume [Nm3/h] Gas volume at normal condition 15 °C 1013 mbar Boiler output [kW] 770 kW Lower calorific value of gas [kWh/m 9.45 kWh/m Natural gas under normal conditions 15 °C 1013 mbar, EN 676 η...
  • Page 23: Settings

    BENTONE Settings Setting the combustion assembly The burner is equipped with a lever that changes the position of the brake plate in the combustion head. This is used to set the correct pressure drop across the combustion assembly and thereby obtain good combustion without ripples.
  • Page 24: Setting The Air Pressure Switch

    BENTONE Setting the air pressure switch The air pressure switch must block the burner if the amount of air for combustion becomes too low. The air pressure switch must be set so that in the event of a lack of air supply at the burner’s max. or min. capacity reacts before the monitored pressure drops so much that poor combustion occurs.
  • Page 25: Setting The Gas Pressure Switch, Min

    BENTONE Setting the gas pressure switch, min. The gas pressure switch must react to too low a connection pressure to the burner, prevent the burner from starting and stop the burner during operation. The burner may start again when the connection pressure has risen above the set pressure on the gas pressure switch.
  • Page 26: Settings Damper Motor, 2-Stage

    BENTONE Settings Damper motor, 2-stage Air adjustment High load • Set control switch for load position to position I The damper motor rotates the air damper between (low load). three preset positions: completely closed, low load and high load. These positions are controlled in the motor Turn red cam disc to 0°...
  • Page 27: Gas Valve, Multibloc Zrdle 405-420

    BENTONE Gas valve, MultiBloc ZRDLE 405-420 All gasline components shall be assembled and mounted without bending, torque and outher mechanical or thermal stress. Gas pressure switch Max. inlet pressure: 360 mbar. Adjustable governor pressure: Inlet pressure 405 - 412 S50 = 4 - 50 mbar...
  • Page 28 BENTONE Adjustment of start gas flow Flow adjustment 2-stage design For stage 1, loosen the lock screw a. Turn the hydraulic Remove the protective cover c. device e: Turn the adjustment knob d (use the protective cover as a to the right = the gas flow is reduced tool) to the desired start gas flow.
  • Page 29 BENTONE 7.6.1 Pressure taps 1,2,3,4,5 1/8 screwed sealing plug 7.6.2 Electrical connection S 20/S 50...
  • Page 30: Service

    BENTONE Service Service and maintenance work may only be performed by qualified personnel. Perform operational check of all safety systems and components at each service. Only CTC original parts should be used when replacing components. Use caution when operating the burner, surfaces may be hot.
  • Page 31: Combustion Device

    BENTONE Combustion device Disconnect the main power and shut off the fuel supply. Before obtaining access to electrical and fuel line components all supply circuits must be disconnected. Remove cover (A), disconnect ignition and ionization cables and control arm (B) from nozzle assembly.
  • Page 32: Air Damper

    BENTONE Air damper Disconnect the main power and shut off the fuel supply. Before obtaining access to electrical and fuel line components all supply circuits must be disconnected. Remove cover (A), disconnect ignition and ionization cables and control arm (B) from nozzle assembly.
  • Page 33: Replacement, Damper Motor Air

    BENTONE Replacement, Damper motor air Disconnect the main power and shut off the fuel supply. Before obtaining access to electrical and fuel line components all supply circuits must be disconnected. Note the connection position of cables to the damper motor.
  • Page 34: Fan

    BENTONE Disconnect the main power and shut off the fuel supply. Before obtaining access to electrical and fuel line components all supply circuits must be disconnected. Detach the electrical panel (Y). Loosen the motor electrical connection and screws (X) enough to turn and lift out the motor.
  • Page 35: Vibrations

    BENTONE Vibrations Maximum permitted vibration level is 5.0 mm/s. • Check tightness of fasteners. • Check fan wheel for damage and contamination (replace if necessary). • Check motor shaft and bearings. If they are worn, replace the motor. Use screw to attach the...
  • Page 36: Control Of Flame Monitoring And Ionization Current

    BENTONE Control of flame monitoring and ionization current The burner is monitored in the standard version according to the ionization principle. The ionization current must be checked at each service occasion. The ionization current is measured with a microampermeter (µA) which is connected in series with the flame electrode and the gas burner control.
  • Page 37 BENTONE 8.8.2 UV –detector (QRC) The UV sensor should not be exposed to temperatures higher than 60 °C. The current passing through the UV sensor when it is lighted must be at least 70 µA. The current can be measured using a rotary coil instrument. A check is necessary only if a malfunction is suspected.
  • Page 38: Replacement Of Electrical Components

    BENTONE Replacement of electrical components Disconnect the main power and switch off the fuel supply. Before obtaining access to terminals, all supply circuits must be disconnected. Note the connection of the existing component and disassemble. Fit new component with same connection or with specified alternative connection.
  • Page 39: Handing Over Of The Installation

    BENTONE Handing over of the installation • Make repeated start attempts to ensure that the adjustments function. • Close the ball valve during operation to check that the gas switch switches off at the set value. • Remove the hose for the air pressure switch to check that the burner locks out.
  • Page 40: 10. Troubleshooting

    BENTONE 10. Troubleshooting Conditions favourable to trouble-free operation of the system can only be guaranteed through the interaction between three factors: electricity, gas flow and combustion air. If any of these factors change, it may cause a malfunction. Before requesting servicing, check the following points: Are the system’s gas taps open?
  • Page 41 BENTONE Cause of fault Action Burner trips during pre-aeration: Air sensor faulty or incorrectly set. Increase/decrease air setting. Reduce air volume. Ignition load incorrectly set. Increase/decrease gas supply Reduce airflow. Gas pressure too low. Increase pressure. If necessary, contact gas supplier.
  • Page 42: 11. Service- And Inspection Protocol

    11. Service- and inspection protocol Installation: Boiler: Name: Type: Efficiency kW: Address: Burner Type: Efficiency kW: Installed by: Date: Date Efficiency gas/h Governor Fluegas Ionisation Pressure temp current Fire room Chimney Measure- ment Before After °C µ A mbar mbar Small Flame Large Flame...
  • Page 43 EU Declaration of conformity Bentone Gas Burners Certificate No. Certificate No. Type: Type: BFG 1 CE-0123CT1269 BG 550 CE-0123CT1326 STG 120 CE-0123CT1270 BG 650 CE-0123CT1348 STG 146 CE-0123CT1281 BG 700 CE-0123CT1359 BG 300 CE-0123CT1292 BG 800 CE-0123CT1360 BG 400 CE-0123CT1304...
  • Page 44 UK Declaration of conformity Bentone Gas Burners Type: BFG 1 BG 300 BG 550 BG 800 STG 120 BG 400 BG 650 BG 950 STG 146 BG 450 BG 700 This declaration of conformity is issued under the sole responsibility of the manufacturer.
  • Page 48 CTC AB Box 309 SE-341 26 Ljungby info@bentone.se +46 372 88 000 www.bentone.se...

This manual is also suitable for:

Lme22.232c2eBg 650-2

Table of Contents