Siemens I-T-E Sensitrip MD Series Information And Instruction Manual page 23

Molded case circuit breakers
Table of Contents

Advertisement

I-T-E Connecting Studs (RS5785, RS5786)
F
Remove the positioning template.
G. Mount the circuit breaker by positioning it over the rear
busbar mounting pads. Attach each pole (Line and
Load) of the circuit breaker to the connecting busbars
with the two 5/16-18 hex head cap screws, flatwashers
and lockwashers (4) (Figure 4). Torque each screw to 72
in. lb.
H. Insert the end shields (7) into the slots provided at the line
and load ends of the breaker (Figure 4).
I.
Replace the breaker terminal shields, (1) on the line and
load side of the circuit breaker and secure with four
breaker terminal shield screws (2). Tighten to 12 in. lb.
(Figure 3).
J.
Affix label (8) (This device is equipped with rear connect-
ing studs) to the front of the circuit breaker (Figure 3).
Figure 6
2 1

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

I-t-e sensitrip nd seriesI-t-e sensitrip smd69600aI-t-e sensitrip smd69700aI-t-e sensitrip smd69800aI-t-e sensitrip smd69600agI-t-e sensitrip smd69700ag ... Show all

Table of Contents