TABLE 7: COOLING CAPACITIES FOR DJ180 AT 115°F
RETURN AIR
GROSS
WB
CFM
CAPACITY
TEMP °F
(MBH)
72
178.8
163.6
67
4500
154.2
62
152.0
57
183.3
72
167.7
67
5250
158.1
62
155.8
57
187.8
72
171.8
67
6000
161.9
62
159.6
57
193.0
72
176.5
67
6750
166.4
62
164.0
57
198.1
72
181.3
67
7500
170.9
62
168.4
57
1. The capacities are gross ratings. For net capacity, deduct the supply air blower motor heat, MBH = 3.415 x kW. Refer to the appro-
priate blower performance table for the kW of the supply air blower motor.
2. These ratings include condenser fan motor and compressor motor power but not the supply air blower motor power.
16
OUTDOOR AMBIENT TEMPERATURE (°F): 115
INPUT
1
2
POWER
(kW)
86
17.24
107.6
16.78
137.2
16.31
154.2
16.24
152.0
17.38
119.6
16.91
152.0
16.44
158.1
16.37
155.8
17.52
131.7
17.05
166.8
16.57
161.9
16.50
159.6
17.53
142.5
17.06
174.0
16.59
166.4
16.52
164.0
17.55
153.3
17.08
181.3
16.60
170.9
16.54
168.4
GROSS SENSIBLE CAPACITY
(RETURN AIR DRY BULB TEMP. - (°F) )
83
80
77
94.7
81.9
69.1
124.4
111.6
98.8
144.3
131.5
118.7
148.0
135.1
122.3
104.5
89.3
74.1
136.8
121.7
106.5
153.1
143.4
128.2
153.8
147.4
132.2
114.2
96.7
79.2
149.3
131.8
114.3
161.9
155.3
137.8
159.6
159.6
142.1
122.6
102.6
82.7
159.8
139.8
119.9
166.4
163.1
143.2
164.0
164.0
144.1
130.9
108.6
86.2
170.3
147.9
125.6
170.9
170.9
148.5
168.4
168.4
146.0
036-21410-001-A-0502
1
(MBH)
74
71
68
56.2
#N/A
#N/A
85.9
73.1
60.3
105.9
93.0
80.2
109.5
96.6
83.8
59.0
#N/A
#N/A
91.3
76.2
61.0
113.1
97.9
82.8
117.0
101.9
86.7
61.7
#N/A
#N/A
96.8
79.3
61.8
120.3
102.8
85.3
124.6
107.1
89.6
62.8
#N/A
#N/A
100.0
80.1
60.1
123.2
103.3
83.4
124.1
104.2
84.3
63.8
#N/A
#N/A
103.2
80.8
58.5
126.2
103.8
81.5
123.7
101.3
79.0
Unitary Products Group