York 359583-YTG-B-0208 Technical Manual

York 359583-YTG-B-0208 Technical Manual

High-efficiency water source heat pumps and water cooled air conditioners horizontal & vertical models 1/2 - 5 tons

Advertisement

Quick Links

TECHNICAL GUIDE
HIGH-EFFICIENCY
WATER SOURCE HEAT PUMPS
AND WATER COOLED
AIR CONDITIONERS
HORIZONTAL & VERTICAL MODELS
1/2 - 5 TONS
GENERAL
All Models 1/2 - 5 tons ship as factory-charged packages.
Horizontal units are designed for suspended ceiling mount-
ing. Horizontal models are shipped with 'straight-through'
evaporator fan discharge as standard. Fan orientation is
field convertible to side discharge. Vertical units are
designed for free-standing floor mounting. All units are
completely factory wired and pre-piped. Water supply,
water outlet, and condensate drain connections are via
female pipe thread fittings.
CABINET
All cabinets are completely constructed of 18 Ga. corrosion
resistant "Galvalume" coated steel. The horizontal units are
complete with integral hanger channels. The entire unit
interior (both evaporator and condensing section) is insu-
lated with 1/2" thick, 2 lb. density insulation. Service panels
are equipped with lifting handles for ease of removal and
handling. All units provide excellent service access to the
reversing valve, thermal expansion valve, and compressor
with the unit remaining in location. An integral duct collar is
provided on the blower discharge opening. An optional dis-
charge plenum is available for Vertical models.
REFRIGERANT CIRCUITS
All models utilize hermetic rotary or reciprocating type com-
pressors. Compressors are mounted on rubber isolators to
minimize vibration transmission. Internal overload protec-
tion is provided. External high pressure and low pressure
cutout switches are included in each compressor control
circuit. Each refrigeration circuit includes an adjustable bi-
flow thermal expansion valve (with external equalizer),
bi-flow liquid line filter drier, and service gauge ports. The
reversing valve is a pilot operated, sliding piston type with a
replaceable magnetic solenoid coil.
The refrigerant-to-air heat transfer coils are constructed of
internally enhanced copper tubes mechanically bonded to
enhanced aluminum plate fins. The evaporator coil is
employed in a draw-through configuration. Large evapora-
tor coil face area minimizes potential water blow-off.
The coaxial refrigerant-to-water heat exchangers feature a
convoluted inner tube design for high heat transfer effi-
ciency. Standard models feature a copper inner tube sur-
rounded by a steel outer tube, and carry a 400 psig water
side working pressure rating.
359583-YTG-B-0208

Advertisement

loading
Need help?

Need help?

Do you have a question about the 359583-YTG-B-0208 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for York 359583-YTG-B-0208

  • Page 1 The coaxial refrigerant-to-water heat exchangers feature a convoluted inner tube design for high heat transfer effi- ciency. Standard models feature a copper inner tube sur- rounded by a steel outer tube, and carry a 400 psig water side working pressure rating. 359583-YTG-B-0208...
  • Page 2: Product Nomenclature

    AC = Cooling only (No Reversing Valve) AD = Cupro Nickle Heat Exchanger AE = Condensate Overflow Switch w/ Alarm output AF = Remote Management Relay Pkg w/ Alarm output 359583-YTG-B-0208 Product Generation 1 = First Generation Installation Options L = Left Hand Return...
  • Page 3 359583-YTG-B-0208 TABLE 1: GENERAL DATA Model Series Nominal Cooling (Ton) Cooling Performance Cooling Capacity (BTUH) 7000 12.4 Heating Capacity (BTUH) 8800 Design CFM Nominal Waterflow (gpm) Compressor-Type Rotary Number Used Air Coil- Type Face Area (sq. Ft.) 1.00 Rows/FPI 2/14...
  • Page 4 0.986 1.058 0.969 0.966 0.993 1.029 0.985 0.983 1.000 1.000 1.000 1.000 1.007 0.977 1.014 1.011 1.010 0.965 1.021 1.017 359583-YTG-B-0208 Heating (db) (MBH) 0.59 0.63 0.67 0.60 0.64 0.68 0.62 0.66 0.70 0.63 0.67 0.71 0.65 0.69 0.73 0.66 0.70...
  • Page 5 359583-YTG-B-0208 TABLE 3: RP 009 @ 300 CFM NOMINAL AIRFLOW VERTICAL AND HORIZONTAL MODELS (ºF) (PSI) (db/wb) (MBH) 75/62 1.35 80/67 10.0 85/72 10.8 75/62 2.25 80/67 10.2 85/72 11.1 75/62 1.35 80/67 85/72 10.5 75/62 2.25 80/67 85/72 10.7 75/62 1.35...
  • Page 6 0.986 1.058 0.969 0.966 0.993 1.029 0.985 0.983 1.000 1.000 1.000 1.000 1.007 0.977 1.014 1.011 1.010 0.965 1.021 1.017 359583-YTG-B-0208 Heating (db) (MBH) 11.7 0.87 11.6 0.93 11.4 0.98 12.4 0.90 12.3 0.96 12.1 1.01 13.1 0.92 12.9 0.98 12.8...
  • Page 7 359583-YTG-B-0208 TABLE 5: RP 018 @ 600 CFM NOMINAL AIRFLOW VERTICAL AND HORIZONTAL MODELS (ºF) (PSI) (db/wb) (MBH) 75/62 18.4 2.75 80/67 20.2 85/72 21.8 75/62 18.7 4.50 80/67 20.6 85/72 22.3 75/62 17.8 2.75 80/67 19.6 85/72 21.2 75/62 18.0...
  • Page 8 0.986 1.058 0.969 0.966 0.993 1.029 0.985 0.983 1.000 1.000 1.000 1.000 1.007 0.977 1.014 1.011 1.010 0.965 1.021 1.017 359583-YTG-B-0208 Heating (db) (MBH) 21.0 1.43 20.7 1.53 20.5 1.62 21.8 1.46 21.5 1.56 21.3 1.65 23.8 1.50 23.4 1.61 23.1...
  • Page 9 359583-YTG-B-0208 TABLE 7: RP 030 @ 1000 CFM NOMINAL AIRFLOW VERTICAL AND HORIZONTAL MODELS (ºF) (PSI) (db/wb) (MBH) 75/62 32.8 80/67 36.2 85/72 39.5 75/62 33.7 80/67 37.1 85/72 40.5 75/62 31.2 80/67 34.5 85/72 37.5 75/62 32.0 80/67 35.5 85/72 38.7...
  • Page 10 0.986 1.058 0.969 0.966 0.993 1.029 0.985 0.983 1.000 1.000 1.000 1.000 1.007 0.977 1.014 1.011 1.010 0.965 1.021 1.017 359583-YTG-B-0208 Heating (db) (MBH) 31.4 2.20 31.0 2.35 30.7 2.49 32.8 2.24 32.3 2.39 32.0 2.53 36.0 2.33 35.4 2.49 34.9...
  • Page 11 359583-YTG-B-0208 TABLE 9: RP 048 @ 1600 CFM NOMINAL AIRFLOW VERTICAL AND HORIZONTAL MODELS (ºF) (PSI) (db/wb) (MBH) 75/62 51.2 80/67 56.9 85/72 59.9 75/62 52.2 12.0 80/67 58.0 85/72 62.1 75/62 48.4 80/67 53.7 85/72 56.7 75/62 49.8 12.0 80/67 55.4...
  • Page 12 0.986 1.058 0.969 0.966 0.993 1.029 0.985 0.983 1.000 1.000 1.000 1.000 1.007 0.977 1.014 1.011 1.010 0.965 1.021 1.017 359583-YTG-B-0208 Heating (db) (MBH) 52.0 3.88 51.3 4.13 50.8 4.38 56.9 4.05 15.0 56.1 4.32 55.6 4.59 59.0 4.12 58.2 4.39...
  • Page 13: External Static Pressure (In W.g.)

    359583-YTG-B-0208 TABLE 11: BLOWER PERFORMANCE Unit Speed High High High High High High 1150 High 1355 1200 High 1880 High 2340 2040 Units are shipped pre-wired for Medium speed. All airflow ratings are at lowest voltage rating of dual rating (i.e.208 volt).
  • Page 14: Service Doors

    359583-YTG-B-0208 SERVICE DOORS 1 - Electrical Box Service Door 2 - Compressor and Condenser Service Door 3 - Blower Service Door RETURN AIR MODEL DIMENSIONS IN INCHES FIGURE 1 - HORIZONTAL DIMENSIONAL DATA Johnson Controls Unitary Products...
  • Page 15 359583-YTG-B-0208 SERVICE DOORS 1 - ELECTRICAL BOX SERVICE DOOR 2 - COMPRESSOR AND CONDENSER SERVICE DOOR 3 - BLOWER SERVICE DOOR FIGURE 2 - VERTICAL DIMENSIONAL DATA Johnson Controls Unitary Products...
  • Page 16 Subject to change without notice. Printed in U.S.A. 359583-YTG-B-0208 Copyright © 2008 by Johnson Controls, Inc. All rights reserved. Supersedes: 359583/036-21486-001-A-1102 Johnson Controls Unitary Products 5005 York Drive Norman, OK 73069...