COOLING PERFORMANCE

SUCT. T/P
@ COMPR.
MODEL
TEMP. PSIG MBH KW MBH KW MBH KW
35
61.5
40
68.5
FRCS0241BD
45
76.0
50
84.0
35
61.5
40
68.5
FRCS0301BD
45
76.0
50
84.0
35
61.5
40
68.5
FRCS0361CD
45
76.0
50
84.0
1. For condensing unit only. Does not include effect of evaporator motor power or heat.
2. Performance based on 15° superheat and 15° sub-cooling at condensing unit.
a. Increase capacity 1% for each 2° increase in sub-cooling.
b. Decrease capacity 1% for each 2° decrease in sub-cooling.
3. Sub-cooling in excess of 20° may result in excessively high condensing temperature with air on condenser above 115°. Maximum recommended
condensing temperature is 140°F.
ACCESSORIES
Refer to Price Manual for specific model numbers.
Compressor Blanket - Designed to further reduce the nor-
mal operating sound and is required to meet Canadian sound
levels for units of three tons and below.
Refer to Price Manual for specific model numbers.
Blower Time Delay - Available to increase efficiency when
installed. Installs on indoor section and maintains blower for
approximately one minute after cooling thermostat has been
satisfied.
TXV KIT - 1TV0700 series must be used to obtain system
performance. See Tabular Data Sheet for proper selection.
Room Thermostats - One of the following thermostat may
be used with these systems.
6
AIR TEMP ON CONDENSER
75×F
95×F
115×F
22.9 1.42 19.4 1.63 15.9 1.82
25.3 1.45 21.6 1.67 18.0 1.90
28.0 1.47 24.0 1.72 20.1 1.97
30.7 1.49 26.5 1.76 22.3 2.04
26.5 1.76 22.9 1.99 19.2 2.11
29.4 1.77 25.6 2.03 21.7 2.19
32.5 1.77 28.4 2.07 24.3 2.27
35.8 1.76 31.4 2.10 27.0 2.33
32.0 1.96 29.2 2.44 26.3 3.10
34.8 1.97 31.9 2.45 28.8 3.11
37.7 1.99 34.7 2.47 31.5 3.12
40.7 2.01 37.6 2.48 34.3 3.13
SUCT. T/P
@ COMPR.
MODEL
TEMP. PSIG MBH KW MBH KW MBH KW
35
61.5
40
68.5
FRCS0421CE
45
76.0
50
84.0
35
61.5
40
68.5
FRCS0481CE
45
76.0
50
84.0
35
61.5
40
68.5
FRCS0601BF
45
76.0
50
84.0
6TH07700124 - One Stage Heat / One Stage Cool, non-pro-
grammable thermostat, manual changeover with automatic
fan on cooling or cooling and heating.
3110-350P - One Stage Heat / One Stage Cool, manual
changeover, non-programmable thermostat.
6ET07700324 - One Stage Heat / One Stage Cool, electronic
programmable (5 day/2 day) manual changeover.

SOUND RATINGS

UNIT MODEL
DECIBELS
024
030
036
042
048
060
* Includes Blanket
AIR TEMP ON CONDENSER
75×F
95×F
36.1 2.31 31.7 2.94 27.5 3.81
39.3 2.33 34.6 2.95 30.1 3.81
42.6 2.35 37.7 2.97 32.9 3.83
46.1 2.39 40.9 3.00 35.8 3.84
43.2 2.64 38.2 3.31 33.2 4.22
47.0 2.66 41.6 3.34 36.4 4.24
50.9 2.69 45.2 3.37 39.7 4.28
54.9 2.72 48.9 3.39 43.0 4.31
52.4 3.09 46.8 3.83 41.2 4.82
56.8 3.11 51.0 3.87 45.1 4.86
61.4 3.15 55.3 3.91 49.2 4.91
66.2 3.18 59.8 3.96 53.3 4.96
SOUND
RATINGS
76*
76*
76
76
76
80
Unitary Products Group