Page 1
INSTALLATION INSTRUCTION SINGLE PACKAGE AIR CONDITIONERS AND SINGLE PACKAGE ELECTRIC UNITS TABLE OF CONTENTS DM090 THROUGH 150 GENERAL ......6 SAFETY CONSIDERATIONS .
Page 2
035-17311-000 REV A (1200) TABLE OF CONTENTS PROTECTION ....... . 30 CONTINUOUS BLOWER .
Page 3
035-17311-000 REV A (1200)) LIST OF FIGURES PG. # PG. # 1 UNIT SHIPPING BRACKET ....7 17 FIELD WIRING 24 VOLT THERMOSTAT ..16 2 CONDENSER COVERING .
Page 4
035-17311-000 REV A (1200) LIST OF TABLES PG. # PG. #\ 1 PRODUCT NOMENCLATURE ....5 18 10T STD MTR DOWN SHOT BLWR PERF ..22 19 10T OPT MTR DOWN SHOT BLWR PERF .
035-17311-000 REV A (1200)) D M 120 C 00 A 3 A AA 1 A TABLE 1: PRODUCT NOMENCLATURE Model Number Model # Options Description D = Air Conditioner, Single Package Product Category M = Standard Efficiency Product Identifier Nominal Cooling Capacity 090 = 7-1/2 Ton 120= 10 Ton 150 = 12-1/2 Ton...
Additional information is available in the following reference forms: GENERAL • - Technical Guide YORK Predatorunits are single package air conditioners • - General Installation designed for outdoor installation on a rooftop or slab and for • - Pre-start & Post-start Check List non-residential use.
035-17311-000 REV A (1200)) INSTALLATION This product must be installed in strict compliance with the enclosed installation instructions and any Toolless applicable local, state and national codes includ- Doorknobs ing, but not limited to, building, electrical, and mechanical codes. Installation PRECEDING INSTALLATION Instruction Packet...
(3 sides) Roof curbs in eight- and fourteen-inch and lifting holes) heights. Roof curbs for transitioning from York Sunline™ footprint to the DM Series footprint are also available Side entry power Tool-less door (field-installed accessory) and control wiring...
If a unit is to be installed on a roof curb other than FIGURE 6 : UNIT 4 POINT LOAD a YORK roof curb, gasketing must be applied to all surfaces that come in contact with the unit under- side.
035-17311-000 REV A (1200)) FIGURE 10 : UNIT DIMENSIONS NOTE: A one-inch clearance must be provided between any combustible material l and the supply ductwork for a distance of 3 feet from the unit. Do not permit overhanging structures or shrubs to DETAIL A DETAIL B obstruct condenser air discharge outlet, combus-...
035-17311-000 REV A (1200) DUCTWORK Ductwork should be designed and sized according to the methods in Manual D of the Air Conditioning Contractors of America (ACCA) or as recommended by any other recog- nized authority such as ASHRAE or SMACNA. A closed return duct system should be used.
A disconnect must be utilized for these units. Factory installed disconnects are available. If installing a disconnect (field supplied or York International supplied accessory), refer to Figure 4 for the recommended mounting location. Avoid damage to internal components if drilling holes for disconnect mounting.
TABLE 12: PREDATOR 380V -3-60 HZ Minimum Circuit Max Fuse Size w/ MCA W/ Power Exhaust Max Fuse Size * Ampacity Pwr. Exh. * OD Fan Model Compressors Motor, Supply Blower Pwr Exh Motors Motor Electric Heater Rated Actual Heater Amps Amps Amps...
035-17311-000 REV A (1200) TABLE 13: PHYSICAL DATA Models Component Blower, Centrifugal (Dia. X Wd. in.) 15 x 15 15 x 15 15 x 15 Evaporator Motor, Standard (HP) 1-1/2 Blower Motor, Optional (HP) Rows Fins per Inch Evaporator Coil Height (in.) 10.6 13.2...
035-17311-000 REV A (1200)) FIGURE 19 : ENTHALPY SET POINT CHART SET POINT ADJUSTMENT The enthalpy set point for the dampers may now be set by selecting the desired setpoint. Adjust as follows: Extreme care must be exercised in turning both the setpoint and minimum position adjusting •...
035-17311-000 REV A (1200) START-UP PHASING Predator units are properly phased at the factory. Check for proper compressor rotation. If the blower or compressors rotate in the wrong direction at start-up, the electrical connec- tion to the unit is misphased. Change the incoming line con- nection phasing obtain...
Page 21
035-17311-000 REV A (1200)) TABLE 16: 7-1/2 TON STANDARD MOTOR DOWN SHOT BLOWER PERFORMANCE TURNS OPEN 3715 1573 1.69 3634 1434 1.54 3431 1265 1.36 3218 0.97 3024 1.05 3650 1657 1.78 3510 1490 1.60 3320 1313 1.41 3079 1145 1.23 2832 0.87...
Page 22
035-17311-000 REV A (1200) TABLE 18: 10 TON STANDARD MOTOR DOWN SHOT BLOWER PERFORMANCE TURNS OPEN 3896 1639 1.76 3688 1453 1.56 3447 1268 1.36 4040 2076 2.23 4005 1934 2.07 3790 1698 1.82 3569 1508 1.62 3333 1330 1.43 3057 1147 1.23...
Page 23
035-17311-000 REV A (1200)) TABLE 20: 12-1/2 TON STANDARD MOTOR DOWN SHOT BLOWER PERFORMANCE TURNS OPEN 5078 3630 3.89 4809 3103 3.33 4594 3053 3.27 4360 2478 2.66 4090 2093 2.24 3812 1798 1.93 4865 3456 3.71 4584 2961 3.17 4349 2912 3.12...
Page 24
035-17311-000 REV A (1200) TABLE 22: 7-1/2 TON STANDARD MOTOR SIDE SHOT BLOWER PERFORMANCE TURNS OPEN 3736 1476 1.58 3487 1284 1.38 3231 1109 1.19 3001 1.04 3572 1514 1.62 3389 1339 1.44 3094 1151 1.23 2764 1.04 2446 0.88 3422 1558 1.67...
035-17311-000 REV A (1200) TABLE 28: INDOOR BLOWER SPECIFICATIONS MOTOR MOTOR SHEAVE BLOWER SHEAVE MODEL BELT Eff. Frame Datum Dia. (in.) Bore (in.) Model Datum Dia. (in.) Bore (in.) Model 1-1/2 1725 1.15 3.4 - 4.4 1VM50 AK94 DM090 1725 1.15 3.4 - 4.4 1VM50...
035-17311-000 REV A (1200)) TABLE 29: MOTOR SHEAVE DATUM DIAMETERS Measure the system Amperage draw across all legs of 3 phase power wires. 1VM50x7/8 1VP56x1-1/8 (1-1/2, 2 & 3 HP Motor) (5 HP Motor) Measure the condenser fan amps draw. Datum Datum Turns Open...
035-17311-000 REV A (1200) The unit control board monitors the temperature limit switch If there is an initial call for both stages of cooling, the UCB will of electric heat units. delay energizing compressor #2 by 30 seconds in order to avoid a power rush.
035-17311-000 REV A (1200)) Should a low-pressure switch open three times within one Remove the call for cooling, by raising thermostat setting hour of operation, the UCB will lock-out the associated com- higher than the space temperature. This resets any pressure pressor and flash a code (Table 33).
035-17311-000 REV A (1200)) NORMAL MAINTENANCE TROUBLESHOOTING Troubleshooting of components may require open- Prior to any of the following maintenance proce- ing the electrical control box with the power con- dures, shut off all power to the unit to prevent per- nected to the unit.
035-17311-000 REV A (1200) TABLE 33: UNIT CONTROL BOARD FLASH CODES Flash Code Description On Steady Control Failure - Replace Control Heart Beat Normal Operation 1 Flash Not Applicable 2 Flashes Control waiting ASCD 3 Flashes HPS1 - Compressor Lock out 4 Flashes HPS2 - Compressor Lock out 5 Flashes...
035-17311-000 REV A (1200)) Monitored Loss of Call for Heat Off Systems Programming? Call for Heating? Problem? Heating? Program Call for 2nd Unit Call for Trip/Failure Stage Control Heat Cooling Board Energize ID Call for First Monitor Blower Motor Cooling? Stage? Call for 1st Turn off ID...
035-17311-000 REV A (1200)) COOLING OPERATIONS If installed, check the position of the economizer blades. If the blades are open, the economizer is providing free On calls for cooling, if the compressors are operating but the cooling and the compressors will not immediately oper- supply air blower motor does not energize after a short delay ate.
Page 38
These options are not enabled by default. Local minals. York distributors can test the UCB for this programming. If 24 volts is present at the UCB Y2 terminal and none of 15. If none of the above corrected the error, test the integrity the protection switches have opened, the UCB may have of the UCB.
Page 39
These options are not enabled by default. Local remove any call for cooling. This will reset any compres- York distributors can test the UCB for this programming. sor lock outs. 12. If none of the above corrected the error, test the integrity NOTE: While the above step will reset any lock outs, com- of the UGB.
Page 40
035-17311-000 REV A (1200) Unitary Products Group...