Power Wiring
Line 1
Field Power
Line 2
Line 3
Supply
Earth
Ground
NOTES:
1. All field wiring must be provided through a field-supplied fused disconnect switch to the unit terminals (or optional molded
disconnect switch).
2. All electrical wiring must be made in accordance with all N.E.C. and/or local code requirements.
3. Minimum Circuit Ampacity (MCA) is based on U.L. Standard 1995, Section 36.14 (N.E.C. Section 440.34).
4. Maximum Dual Element Fuse size is based on U.L. Standard 1995, Section 36.15 (N.E.C. Section 440.22)
5. Use copper conductors only.
6. On units with an optional disconnect switch, the supplied disconnect switch is a "Disconnecting Means" as defined in the N.E.C. Section
100, and is intended for isolating the unit from the available power supply to perform maintenance and troubleshooting. This disconnect
switch is not intended to be a Load Break Device.
FIG. 3 – SINGLE-POINT POWER SUPPLY WIRING WITH NON-FUSED DISCONNECT
32
(continued)

SINGLE-POINT POWER SUPPLY WIRING

WITH NON-FUSED DISCONNECT
Electrical / Controls Box
Power Side
Molded
Case
Disconnect
Switch
Control Side
Wiring Terminal
Block
LD06415