Specifications
Standards and EC Directives
Conforms to the following EC Directives:
• Machinery Directive
• Low Voltage Directive
• EN 1088
• EN 60204-1
• GS-ET-19
• CCC
Certified Standards
Certification
Standard
body
EN 60947-5-1
TÜV SÜD
(certified direct opening)
UL *1
UL 508, CSA C22.2 No.14
CQC (CCC)
GB14048.5
KOSHA *2
EN60947-5-1
*1. CSA C22.2 No. 14 was certified by UL.
*2. Only certain models have been certified.
Certified Standard Ratings
TÜV (EN 60947-5-1)
Item
Utilization category
Rated operating current (Ie)
Rated operating voltage (Ue)
Note: Use a 10 A fuse type gI or gG that conforms to IEC60269 as a
short-circuit protection device. This fuse is not built into the
Switch.
UL/CSA (UL 508, CSA C22.2 No. 14)
A300
Current (A)
Rated
Carry
voltage
current
Make
120 VAC
60
10 A
240 VAC
30
Q300
Current (A)
Rated
Carry
voltage
current
Make
125 VDC
0.55
2.5 A
250 VDC
0.27
File No.
Consult your
OMRON
representative for
details.
2005010305167533
2005-196
AC-15
DC-13
3 A
0.27 A
240 V
250 V
Volt-amperes (VA)
Break
Make
Break
6
7,200
720
3
Volt-amperes (VA)
Break
Make
Break
0.55
69
69
0.27
Solenoid Coil Characteristics
Item
Type
Rated operating voltage
24 VDC
(100% ED)
Current consumption
Approx. 200 mA
Insulation Class
Class F (130°C max.)
Indicator Characteristics
Item
Type
Rated voltage
24 VDC
Current consumption
Approx. 1 mA
Color (LED)
Orange
D4JL
24 VDC
+10%
−15%
LED
24 VDC
Approx. 8 mA
Green
6