Fig. 25 Options for creating a new Modbus register
Register Number: Is incremented automatically and can be changed manually.
Assigned to:
Serial Number:
Transmitter Port: Type in transmitter port (see chapter 6.2.2)
Measurand / Unit: Select measurand and unit.
Failsafe Value:
Data Type:
Factor:
Offset:
Create Register:
Deleting registers:
Click the "Edit" link in the "Modbus Register Map" list to change the configuration of any register.
Click the button "Delete Register" to delete the selected register.
Fig. 26 Deleting a register
User Manual EE240 Wireless Sensor Network
Select whether a sensing probe or a transmitter will be mapped to the register.
(Details see 6.2.3 Outputs → Mapping the selected measurand)
Type in the serial number of the probe or transmitter or copy and paste from the
transmitter list (see chapter 6.2.2)
Set the output value in case of (transmission) error/alarm.
Select data type (Float, Integer,..)
Set the multiplication factor for the register value
(Reg.Value = Current Value * Factor)
Set the offset for the register value (Reg.Value = Current Value * Factor + Offset)
The register will be created with the selected configuration.