PEP Installation
Purpose/Scope
20 min.
Safety Considerations
WARNING
Procedure
WBPEEUI210509A0
This procedure explains how to install the PEP into the
cabinets.
Parts
Number
200037A080A1020
NIDHA16008
NMPCC16002
6644463?1
6644463?2
6644463?3
6644463?4
6644463?5
6644463?6
Tools
Bladed screwdriver.
1. Disconnect power before attempting these procedures. Fail-
ure to do so could result in severe or fatal shock, or equipment
damage.
1. Be sure power is removed at the source before starting this
procedure.
W1
2. Open the front door of the cabinet.
3. Install cage nuts on the 21st and 28th holes from the top
of the cabinet on the front mounting brackets (Fig. PR6-1).
Qty
Description
4
Lockwasher, helical spring, M8
4
Screw, sems ext pan head slot, 0.190-32
4
Nut, cage, 10-32
1
PEP, 120/240 VAC, 25 A, without line filter
PEP, 120/240 VAC, 25 A, with line filter
PEP, 120/240 VAC, 25 A; 125 VDC, 25 A,
without line filter
PEP, 120/240 VAC, 25 A; 125 VDC, 25 A,
with line filter
PEP, 125 VDC, 25 A, without line filter
PEP, 125 VDC, 25 A, with line filter