Table 1-4. Specifications
Property
Fast transient/burst
susceptibility
Transient surge
Electrostatic discharge
Environmental
Temperature
Operating enclosure (int)
Operating enclosure (ext)
Storage and transport
Relative humidity
Operating
Altitude
Operating
Storage and transport
Air quality
Overvoltage category
Vibration
Certifications
Canadian Standards
Association (CSA)
Factory Mutual (FM)
WBPEEUI210509A1
(continued)
Meets IEC 1000-4-4, level 3, mains 2 kV at 5 kHz, outputs
1 kV at 5.0 kHz with no degradation or loss of function.
Meets IEC 1000-4-5, level 3, 2 kV with no degradation or loss
of function.
Meets IEC 1000-4-2, level 3 with no degradation or loss of
function.
0° to 70°C (32° to 158°F) with derating from 50°C (-2.5% per °C)
0° to 55°C (32° to 131°F) with derating from 50°C (-2.5% per °C)
-40° to 85°C (-40° to 185°F)
20% to 90% up to 55°C (131°F) noncondensing
20% to 45% at 55° to 70°C (131° to 158°F) noncondensing
Sea level to 3,048 m (10,000 ft)
Up to 9,144 m (30,000 ft)
Noncorrosive per ISA S71.04 class LA, LB, LC Severity Level 1
IEC 1010-1, Category II or III, for mains
13.2 to 100 Hz, 0.7 G
2 to 13.2 Hz, 12 mm (0.47 in.) peak-to-peak displacement
Certified for use as process control equipment in an ordinary
(nonhazardous) location.
Approval pending for the following categories:
Nonincendive for Class I; Division 2; Groups A,B,C,D T4
CE mark, low voltage directive, EMC Directive when used in
appropriate cabinet
Characteristic/Value
Specifications
1 - 7