Specifications - ABB Symphony Harmony Series Instructions Manual

Hide thumbs Also See for Symphony Harmony Series:
Table of Contents

Advertisement

Specifications

Table 1-4. Specifications
(continued)
Property
Power output
Voltage/current
Load sharing
Line regulation
Load regulation
Hold up time
Power Consumption and
Heat Dissipation (max. values)
1 - 8
Characteristic/Value
Module
Outputs
5
Nominal VDC
5.09
Minimum VDC
5.04
Maximum VDC
5.25
Maximum ripple
100
and noise (mV
)
pp
Current shared equally between modules within 10% (highest
current load to lowest current load) at full load for +5 VDC and
+24 VDC outputs
±0.5% of nominal output voltage over input voltage range
Within specified min and max. outputs from 0% to 100% load
20 msecs following loss of power
Power Supply
P-HA-RPS-00010000
P-HA-RPS-00200000
P-HA-RPS-02010000
P-HA-RPS-02200000
P-HA-RPS-03000000
P-HA-RPS-11000000
P-HA-RPS-11010000
P-HA-RPS-11100000
P-HA-RPS-21000000
P-HA-RPS-21010000
P-HA-RPS-21200000
P-HA-RPS-32000000
2
P-HA-RPS-32010000
2
P-HA-RPS-32200000
P-HA-RPS-40000000
NOTES:
1. 70% of input power converted to output power. 30% of input power
converted to heat dissipated into cabinet.
2. The max. output power for these power supply trays is 816 W.
Rated Voltages (VDC)
+15
-15
24
48
15.10 -15.10 25.50 49.1
14.95 -14.95 24.35 48.5
15.75 -15.75 26.80 49.6
150
150
300
600
Power
Heat Dissipation
Consumption
(BTU/Hr
(Watts)
411
583
994
1,166
1,166
349
760
554
477
888
1,060
1,140
1,166
1,166
1,057
125
125.6
123.1
128.1
1,000
1
)
421
597
1,018
1,194
1,194
357
778
568
489
909
1,086
1,168
1,194
1,194
2,251
WBPEEUI210509A0