Honeywell HA40 Technical Manual page 32

4-channel controller
Table of Contents

Advertisement

HA40 4-Channel Controller
4 Enclosures
The HA40 controller enclosures are shown in Figures 4-1, 4-2, and
4-3. Non-metallic enclosures are not grounded by metal conduit. For
internal ground points to be grounded to earth, the TB5 – GND terminal
must have a proper earth ground connection (see
4.1 HA40PCS NEMA 4/HA40SS NEMA 4X Steel
Enclosures
The HA40PCS (painted carbon steel) and HA40SS (stainless steel)
enclosures are shown in Figure 4.1.
Instrument
Viewing Window
Single 1/4 Turn Latch
Side View
6.20
2.70
0.0
2.40 4.12 5.84 7.56
Figure 4-1. NEMA Painted Carbon Steel or Stainless Steel Enclosure
HA40 Technical Manual
Figure
9.84
8.84
2.56
C L
11.81 12.90 13.65
Front View
1/2 in. NPTConduit Fittings
(Typical 4 places)
Notes:
Material
Part#1000-2377 316 Stainless Steel
Part#1000-2378 Painted Carbon Steel
Bottom View
4.2 HA40PY NEMA 4X Polycarbonate
Enclosure
CAUTION
3-2).
Nonmetallic enclosures do not provide grounding between conduit
connections. Use grounding type bushings and jumper wires. All field wiring
must have insulation suitable for at least 250V.
The HA40PY polycarbonate enclosure is shown in Figure 4.2.