Summary of Contents for ZIEHL-ABEGG UNIcon CPG AVC Series
Page 1
english UNIcon CPG-..AVC Sensor-control module for differential pressure and volume ow Operating Instructions Keep for reference! Software version: from Version 1.00 L-BAL-E286-GB 1904 Index 004 Part.-No. 00163471...
Operating Instructions UNIcon CPG-..AVC General notes 1 General notes Compliance with the following instructions is mandatory to ensure the functionality and safety of the product. If the following instructions given especially but not limited for general safety, transport, storage, mounting, operating conditions, start-up, mainte- nance, repair, cleaning and disposal / recycling are not observed, the product may not operate safely and may cause a hazard to the life and limb of users and third parties.
Operating Instructions UNIcon CPG-..AVC Safety instructions 2 Safety instructions Attention! • Mounting, electrical connection, and start-up operation may only be carried out by an electrical specialist in accordance with electrotechnical regulations (e.g. DIN EN 50110 or DIN EN 60204)! • Persons entrusted with the planning, installation, commissioning and maintenance and servicing in connection with the device must have the corresponding qualifications and skills for these jobs.
Operating Instructions UNIcon CPG-..AVC Product overview 3 Product overview 3.1 Function Sensor-control module with differential-pressure sensors in proven ceramic-cantilever technology for climate and clean-room application. The pressure range from 0 to 6000 Pa (24 in.wg) is covered with 3 types of device. With each type four measuring ranges are programmable.
Operating Instructions UNIcon CPG-..AVC Mounting 4 Mounting • Before installation remove the device from the packing and check for any possible shipping damage! • Assemble the device on a clean and stable base. Do not distort during assembly! Use the appropriate mounting devices for proper installation of the unit! •...
Operating Instructions UNIcon CPG-..AVC Electrical installation 5.2 Connection Voltage supply Connection Voltage supply at terminals: “+U ” and “GND”. Here, it must be strictly observedt hat the mains voltage lies within the llowable olerance pecifications (see Technical data and nameplate affixed to the side). Danger due to electric current Only PELV current sources which ensure safe electrical isolation of the operating voltage in accordance with IEC/DIN EN 60204-1 must be used.
Operating Instructions UNIcon CPG-..AVC Electrical installation 5.4 Digital input (D1) Different functions can be assigned to the digital input D1(see IO SETUP). A voltage at terminals “1” and “2” (10...24 V DC) activates the programmed function (note polarity - see connection diagram). 5.5 Relay outputs “K1”...
Operating Instructions UNIcon CPG-..AVC Electrical installation 5.6 RS-485 interface for MODBUS The device comes equipped with a RS-485 interface for networking via MODBUS. Conntection at: “A (D+)”, “B (D-)” and “GND”. MODBUS MODBUS MODBUS MODBUS (RS-485) (RS-485) (RS-485) (RS-485) (D+) (D-) (D+) (D-)
Page 11
Operating Instructions UNIcon CPG-..AVC Electrical installation Recommended wire types 1. CAT5 / CAT7 cables 2. J-Y (St) 2x2x0.6 (telephone cable) 3. AWG22 (2x2 twisted pair) Max allowed wire length 1000 m (CAT5/7 500 m). Shielding The use of shielded cables is normally not needed but offers high protection against electromagnetic interferences, especially high frequencies.
Operating Instructions UNIcon CPG-..AVC Electrical installation 5.6.1 Automatic addressing Automatic addressing can be started when the connections “ID1” and “ID2” for “Address- ing” are connected with each other additionally next to the bus connection. I. e. it is no longer necessary to address every user manually in the network. (D+) (D-) A-G-247NW...
Operating Instructions UNIcon CPG-..AVC Electrical installation 5.7 Input for outdoor temperature sensor 4.02 5.02 operating modes with setpoint adjustment depending on outdoor temperature, the outdoor temperature sensor is connected at the “TF” terminals. You can connect passive temperature sensors TF... (KTY81-210) or PT1000, and the polarity is not relevant.
Operating Instructions UNIcon CPG-..AVC Device construction 6 Device construction 6.1 Connecting elements 1 Signal relay (terminals: 13, 14) 2 Supply voltage (terminals: U , GND) 3 Output signal 0...10 V (terminals: A, GND) 4 Cable gland M16 + seal insert with two holes (5 mm) 5 "Minus"- connection in area with lower pressure 6 "Plus"- connection in area with higher pressure 7 Digital input D1 (terminals: 1, 2)
Operating Instructions UNIcon CPG-..AVC Modes/Start-up Messages on the display No enable Exceeding measuring range Moon symbol = Adjustment for Setpoint 2 active Hourerglass symbol = Timer function active External fault alarm External error Limit: Modulation Limit Uout Limit: Pressure Limit Pressure Limit: volume flow Limit AirVolume Limit: Temperature...
Operating Instructions UNIcon CPG-..AVC Modes/Start-up 7.2 Start-up Procedure 1. You must mount and connect the device in accordance with the operating instruc- tions. 2. Double check that all connections are correct. 3. The supply voltage must match the information on the rating plate. 4.
Operating Instructions UNIcon CPG-..AVC Programming Proceed as follows: 1. Pull off the pressurised hoses. “Autozero” “ON” 2. Switch function “0” 3. The display switches to the actual value display and the value displayed after zero point calibration has taken place. “0”...
Page 19
Operating Instructions UNIcon CPG-..AVC Programming Additional menu item for mode 4.02 with outside-temperature dependent target- setpoint Outside-temperature dependent target-setpoint An outside temperature compensation can be activated (sensor connection terminals [Pa] "TF-"TF") when being operated as a pres- sure control device. This function automatically changes the set and active “Setpoint 1”...
Operating Instructions UNIcon CPG-..AVC Programming 8.2 Volume sensor 5.00 and volume control 5.01 5.02 8.2.1 Base setup 5.00 5.02 BASE SETUP 5.00 : Volume flow sensor 5.01 5.01 : Volume flow control Mode 5.02 : Volume flow control with outdoor temperature compensation Display in SI units "metric"...
Values for Imperial units (US) 8.2.2 Nozzle coefficient (K-Factor) For the modes 5.00 5.01 the K-factors (SI-units) of the following ZIEHL-ABEGG fans can be taken from the table. For fans not listed here, ask the manufacturer for the K-factor. C-series Size ZAbluefin...
Operating Instructions UNIcon CPG-..AVC Programming C-series Size ZAbluefin Vpro-series M-series ZAvblue Cpro-series 1000 1050 1120 1250 Subject to technical changes! Maximum K-Factor depending on the measuring range of the pressure sensor Range [Pa] 1000 2000 3000 4000 6000 [in.wg] 12.0 16.0 24.0 Max.
Page 23
Operating Instructions UNIcon CPG-..AVC Programming Maximal output voltage 10.0 V Setting range: 10...0 V Max. Uout Factory setting: 10 V Additional menu item for mode 5.02 with outside-temperature dependent target- setpoint Outside-temperature dependent target-setpoint An outside temperature compensation can be activated (sensor connection terminals "TF-"TF") when being operated as a volume flow control device.
Operating Instructions UNIcon CPG-..AVC Programming 8.3 Menu group "INFO" The number of menus depends on the selected operating mode. Settings cannot be made in this menu group! INFO Mode Display 4.00 4.01 4.02 5.00 5.01 5.02 Actual value after turning on the voltage or after exiting the setting menu using the Esc key combination.
Operating Instructions UNIcon CPG-..AVC Programming 8.4.2 Analog outputs “AO” Menu overview Function Designation Setting of the desired function (see following table). Control sign. 2A AO1 Function Analog output A1 (terminals: A, GND) No further assignment possible, n.a. (no assignment) = No signal assigned. AO1 Signal Inverting output AO1 Inverting...
Page 27
Operating Instructions UNIcon CPG-..AVC Programming Fault indication (factory setting) Fault indic. Reports a failure, switch-off using the enable function (see digital inputs “DI”) is not reported. Report of an external failure triggered by digital output (no function in 4.00 Extern. Error. 5.00 Limit message modulation Limit modu.
Operating Instructions UNIcon CPG-..AVC Programming 8.4.4 Digital inputs “DI” The device has three virtual digital inputs: DI1, DI2 and DI3 (not available in 4.00 5.00 8.4.4.1 Menu overview Example for DI1 Function Designation Setting of the desired function (see following table). DI1 Function Allocation: virtuell input <=>...
Operating Instructions UNIcon CPG-..AVC Programming 8.4.4.2 Enable ON/OFF, function Remote ON/OFF (electronic disconnection). The device can still be operated in the switched-off state after pressing the “Esc” key combination. ) does not report the switch- A programmed alarm relay (factory set “K1 function” = off.
Operating Instructions UNIcon CPG-..AVC Programming 8.4.4.3 External message, function Connection of an external fault indication - the device continues operating with no changes after a message and “External Error” appears in the display. Message via relay “K1” depending on programmed function (see digital output “DO”). A programmed alarm relay (factory set “K1 function”...
Operating Instructions UNIcon CPG-..AVC Programming 8.4.4.4 Setpoint 1/2, function Switching between control with Setpoint 1 and Setpoint 2. Setpoint 1active Setpoint 2 active The active Setpoint is indicated in the menu 100 Pa 80 Pa INFO, an active “Setpoint 2” is signalized by the Δp Δp moon symbol.
Operating Instructions UNIcon CPG-..AVC Programming 8.5 Menu group "LIMITS" 8.5.1 Limit message modulation Menu overview Function Designation OFF: no function ON: limit message active The “Limit Uout” message appears in the display if the set limit value for modulation is exceeded. The message via the relay depends on the pro- Level Fuction grammed function (see IO Setup), with the factory setting (K1 function = , not inverted) the relay is de-energised (terminals 13 - 14 disconnected).
Operating Instructions UNIcon CPG-..AVC Programming 8.5.2 Limit message actual value Menu overview Function Designation OFF: no function ON: limit message active The values "Value min." and "Value max." can be set independently of one another. The unit depends on the selected operating mode ( ) and unit (metric / inch).
Operating Instructions UNIcon CPG-..AVC Programming Example for limit message actual value Settings - Value Max.: 800 Pa - Value Min.: OFF Analog IN - switching hysteresis 5 % (from 100 %) 11.05.2007 50 % 100 % v_grenzwert_signal_k1_1.vsd Settings - Value Min.: 200 Pa - Value Max.: OFF Analog IN - switching hysteresis 5 % (from 100 %)
Operating Instructions UNIcon CPG-..AVC Programming Information Always set the value for "Temp max." higher than the value for "Temp min.". Examples for limit messages outdoor temperature Settings - Temp. Max.: 80 °C - Temp. Min.: OFF Analog IN - switching hysteresis 5 % (from 100 %) 11.05.2007 50 % 100 %...
Operating Instructions UNIcon CPG-..AVC Programming Menu overview Parameter Designation Time Press the P-key and set the hours with the UP / DOWN keys, press the P- 15:05 key to save. Time Now the minutes flash and can be set with the UP / DOWN keys, press the P- key to save.
Page 37
Operating Instructions UNIcon CPG-..AVC Programming Menu overview Function Designation Bus Address The device address is factory set to the highest available MODBUS address: 247. Bus Address Setting range MODBUS Address: 1 - 247. UART Baudrate Setting transfer rate 19200 Valid values: 4800, 9600, 19200, 38400, 115200 UART Baudrate Factory setting: 19200 UART Mode...
Operating Instructions UNIcon CPG-..AVC Programming 8.7.2 MODBUS Register 8.7.2.1 Holding register Mode Function/Setting 00 01 02 00 01 02 0 = OFF 1 = Restore factory setting (delivery status) Input MODBUS, digital control bit wise* Digital inputs DI1-3 @ Bit 15, relay K1 @ Bit 14 On register H23 Value 2 = Function 17A: Preset output voltage from analog output “AO”...
Page 39
Operating Instructions UNIcon CPG-..AVC Programming Mode Function/Setting 00 01 02 00 01 02 x Time delay limit message actual value: 0...120 (s) x Limit message outdoor temperature: 0 = OFF, 1 = ON Minimum temperature: -500 = OFF, -500...1500 -50.0...150.0 °C (-580 = OFF, -580...3020 -58.0...302.0 °F) Maximum temperature:...
Operating Instructions UNIcon CPG-..AVC Programming Information The registers HR00, HR01, HR02, HR47, HR51, HR52 and HR53 can be written as often as needed. For all other registers, write processes are limited to 10,000 (i.e. only use them for configuration purposes). Value of the bits Bit 0 Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 Bit 7 Bit 8 Bit 9 Bit 10 Bit 11 Bit 12 Bit 13 Bit 14 Bit 15 0x8000 0x4000 0x2000 0x1000 0x0800 0x0400 0x0200 0x0100 0x0080 0x0040 0x0020 0x0010 0x0008 0x0004 0x0002 0x0001...
Operating Instructions UNIcon CPG-..AVC Enclosure 9 Enclosure 9.1 Technical data Type CPG-200AVC CPG-1000AVC CPG-6000AVC Part-No. 320075 320076 320077 Voltage supply 10...24 V DC (+20 %) Protected against reverse polarity 10 V DC 13...24 V DC Max. load output 0...10 V 0.3 mA 10 mA (short-circuit-proof)
Page 42
Operating Instructions UNIcon CPG-..AVC Enclosure Total of linearity, hysteresis and repeat- ability max. Long term stability according to +/-1.0 +/- 1.0 +/- 1.0 DIN EN 60770 Temperature coefficient typical +/- 0.2 +/- 0.2 +/- 0.2 Temperature coefficient max. +/- 0.4 +/- 0.4 +/- 0.4 Temperature coefficient sensitivity typical % /...
- ventilation technology. phone: +49 (0) 7940 16-800 Email: fan-controls-service@ziehl-abegg.de Our worldwide contacts are available in our subsidiaries for deliveries outside of Ger- many, see www.ziehl-abegg.com. L-BAL-E286-GB 1904 Index 004 Part.-No. 00163471 44/44...
Need help?
Do you have a question about the UNIcon CPG AVC Series and is the answer not in the manual?
Questions and answers