Rheem Solar Premier Loline 596270 Owner's Manual And Installation Instructions page 47

Gas boosted water heater
Hide thumbs Also See for Solar Premier Loline 596270:
Table of Contents

Advertisement

Using a spanner engaged on the valve's spanner flats and applying medium pressure to tighten, turn the
relief valve an additional ½ to 1 ½ turns to secure and make the joint water tight, leaving the valve drain
pointing downwards.
Warning: Do not use a pipe wrench or poor fitting tool on the valve body nor over tighten the valve,
as this could damage the valve and prevent safe operation.
Operate the easing lever on the valve to check the smooth operation of the valve plunger. It is very
important the lever is raised and lowered gently. The lever should move smoothly and without undue force.
If the lever cannot be moved or is jerky in its movement, then the valve has been damaged and must be
replaced.
A copper drain line must be fitted to the temperature pressure relief valve (refer to
page 47).
The valve must be insulated with closed cell polymer insulation or similar (minimum thickness 9 mm) and
the insulation installed so as not to impede the operation of the valve.
The insulation must be weatherproof and UV resistant if exposed.
EXPANSION CONTROL VALVE
Local regulations may make it mandatory to install an expansion control valve (ECV) in the cold water line to
the water heater. In other areas, an ECV is required if the saturation index is greater than +0.4 (refer to
Supplies"
on page 17).
The expansion control valve must always be installed after the non-return valve and be the last valve installed
prior to the water heater
control valve (refer to
"Relief Valve Drain"
The valve, if installed within 500 mm of the water heater, must be insulated with closed cell polymer insulation
or similar (minimum thickness 9 mm) and the insulation installed so as not to impede the operation of the valve.
The insulation must be weatherproof and UV resistant if exposed.
RELIEF VALVE DRAIN
DN15 copper drain lines must be fitted to the temperature pressure relief valve, expansion control valve (if one
is installed) and solar circuit relief valve to carry the discharge clear of the water heater. Connect the drain
lines to the valves using disconnection unions. The drain line from the valve to the point of discharge should
be as short as possible, have a continuous fall all the way from the water heater to the discharge outlet and
have no tap, valves or other restrictions in the pipe work.
A drain line from a relief valve must comply with the requirements of AS/NZS 3500.4.
A drain line must be no longer than nine (9) metres with no more than three bends greater than 45° before
discharging at an outlet or air break. The maximum length of nine (9) metres for a drain line is reduced by
one (1) metre for each additional bend required of greater than 45°, up to a maximum of three additional bends.
Where the distance to the point of final discharge exceeds this length, the drain line can discharge into a
tundish.
Subject to local regulatory authority approval, the drain lines from the temperature pressure relief valve and
expansion control valve from an individual water heater may be interconnected.
The outlet of a drain line must be in such a position that flow out of the pipe can be easily seen, but arranged
so discharge will not cause injury, damage or nuisance. The termination point of a drain line must comply with
the requirements of AS/NZS 3500.4. Drain lines must not discharge into a safe tray.
In locations where water pipes are prone to freezing, drain lines must be insulated, must not exceed 300 mm
in length and are to discharge into a tundish through an air gap of between 75 mm and 150 mm.
If a drain line discharges into a tundish, the drain line from the tundish must be not less than DN20. The drain
line from a tundish must meet the same requirements as for a drain line from a relief valve.
Warning: As the function of the temperature pressure relief valve on this water heater is to discharge high
temperature water under certain conditions, it is strongly recommended the pipe work downstream of the relief
valve be capable of carrying water exceeding 93°C. Failure to observe this precaution may result in damage
to pipe work and property.
(refer to diagram on page
on page 47).
45). A copper drain line must be fitted to the expansion
47
CONNECTIONS – PLUMBING
"Relief Valve Drain"
"Water
on

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents