4. ACCESS LEVELS

Three access levels are used to operate or configure the control and indicating equipment.
4.1.

Access Level 1

Access Level 1 provides open access to perform the following functions:
Acknowledge a new event (and silence the internal sounder).
Override any active delays in the Alarm Condition.
Perform the indicator test.
Place the panel into Access Level 2 or Access Level 3.
4.2.

Access Level 2

Access Level 2 provides access to the following functions for authorized users:
Acknowledge a new event (and silence the internal sounder).
Override any active delays.
Perform the indicator test.
Silence and re-activate alarms (including for a building evacuation).
Reset the fire detection and alarm system.
Disable or enable the following:
Zones
o
Alarms
o
Auxiliary outputs
o
Activate delays (if configured).
4.2.1. Enter Access Level 2
Access Level 2 can only be entered if there are no new events to acknowledge.
To enter the Access Level 2 passcode, take the following actions:
1) Press and hold the ACK button for 3 s. The A1 LED will flash.
2) Enter the Access Level 2 passcode using the DISABLEMENT buttons numbered 1 ~ 4. Each button press
will cause the following indicator to light:
First button press
Second button press
Third button press
Fourth button press
The factory default Access Level 2 passcode is 2244.
3) Press the ACK button to confirm the passcode.
If the passcode is correct:
The internal sounder will give a double short beep.
The A2 LED will flash twice, pause, then repeat.
If the passcode is incorrect:
The internal sounder will give a single long beep.
Indicators B 1 ~ B 4 will turn off.
A new passcode can be entered.
To exit Access Level 2, press HOME, then the ACK button to confirm.
All specifications and other information shown were current at the date of publication and subject to change without notice.
4001 non-addressable control and indicating equipment
4
© 2015 ~ 2018 Ambest Electronics (Ningbo) Co Ltd. All rights reserved.
Installation and Service Manual
B 1
B 2
B 3
B 4
32-0002-r12_2018-09