Ordering Information; Battery Calculations - Numens 4001 Series Installation And Service Manual

Non-addressable 2, 4, 8 zone fire alarm control and indicating equipment
Hide thumbs Also See for 4001 Series:
Table of Contents

Advertisement

Miscellaneous
Terminal wiring
Operating temperature
Operating humidity
Storage temperature
Storage humidity
Dimensions (h × w × d)
Weight (excluding batteries)
For current technical data, refer to the 4001 Control and Indicating Equipment datasheet.
Document number 31-0002.

12.2. Ordering Information

Model
2 Alarm Zone Circuits
4001-01
4001-02
4001-03

12.3. Battery Calculations

Calculate the required battery capacity for the installation using the following formula.
Where:
I
is the total quiescent current (in amps)
Q
t
is the required battery operating time (in hours) when the mains supply is unavailable
S
I
is the total Alarm Condition current (in amps) with all devices operating
A
t
is the required Alarm Condition operating time (in hours) following t
A
All specifications and other information shown were current at the date of publication and subject to change without notice.
4001 non-addressable control and indicating equipment
4 Alarm Zone Circuits
[(I
×t
) + (I
×t
Q
S
A
24
© 2015 ~ 2018 Ambest Electronics (Ningbo) Co Ltd. All rights reserved.
Installation and Service Manual
4001-01
4001-02
(0.4 ~ 2.5) mm
(0 ~ +50) °C
(0 ~ 95) % RH, non-condensing
(-25 ~ +80) °C
(0 ~ 98) % RH, non-condensing
(402 × 337 × 99) mm
4.0 kg
)]×1.2
A
S
4001-03
2
8 Alarm Zone Circuits
32-0002-r12_2018-09