6.10. Ancillary Inputs

There are three remote activation inputs. All remote inputs are activated using a voltage free dry contact like
a relay. Terminate the wiring for each auxiliary input in their respective terminals and the cable screens
connected to earth.
6.10.1. Remote Reset
The momentary closure of a contact at remote reset input will initiate a system reset.
To comply with the requirements of EN 54-2, the remote system reset function must be
activated using a secure method, such as a keyswitch.
6.10.2. Evacuation Start/Stop
Evacuation Start/Stop activates alarms immediately when a short-circuit is applied to the input. The
SILENCE/ACTIVATE ALARMS LED will illuminate when active. Alarms continue to operate until the short-
circuit is removed, or the SILENCE/ACTIVATE ALARMS button is pressed.
6.10.3. Day/Night Mode
A short-circuit applied to the Day/Night Mode input will enable programmed delays (Day Mode). The DELAYS
ACTIVE LED will be illuminated. Removing the short-circuit will disable programmed delays (Night Mode).

6.11. Remote Display Output

This interface has not been assessed for conformance with EN 54-2.
Set the jumper on the 6001-04 Remote LED Display card to display Fire or Fault indications.
Set zone group jumper to A0 to display detection zones 1 ~ 8, or to position A1 to display detection zones
9 ~16.
Install the display card in a suitable enclosure or behind a protective panel.
Install cabling from the 6001-04 Remote Display card to the MPX port on the main board. Terminate the wiring
for each indicator to their respective terminals, and the cable screens connected to earth.
Z1
Z2
Z3

6.12. Detection Zone Output Card

The 6001-07 Detection Zone Output Relay card provides 8 voltage-free, normally-closed relay contact outputs
for detection zones. The relay contacts will open when a detection zone initiates an Alarm Condition.
This interface has not been assessed for conformance with EN 54-2.
Install cabling from the 6001-07 Detection Zone Output Relay card to the MPX port on the main board.
Terminate the wiring for each indicator to their respective terminals, and the cable screens connected to earth.
All specifications and other information shown were current at the date of publication and subject to change without notice.
4001 non-addressable control and indicating equipment
From remote display card
Z4
Z5
Z6
Z7
Z8
MPX
© 2015 ~ 2018 Ambest Electronics (Ningbo) Co Ltd. All rights reserved.
Installation and Service Manual
S1
AUX
FIRE
C
NC
NO
C
NC NO
C
DATA
13
FLT
INPUTS
RESET AUX SP
NC
DE
C
DV
32-0002-r12_2018-09

Hide quick links:

Advertisement

Table of Contents
loading

Related Products for Numens 4001 Series

This manual is also suitable for:

4001-014001-024001-03

Table of Contents