9. COMMISSIONING
9.1.
Control and Indicating Equipment
To commission the control and indicating equipment, undertake the following actions and tests.
1) Activate the mains supply.
2) Fit the batteries, taking care to ensure the correct voltage polarity. The green SUPPLY LED should be the
only indicator illuminated. If fault or other indicators are active, resolve the cause(s) of the indication before
proceeding.
3) Undertake the indicator tests specified in 5.4.1.
4) Configure any required Alarm Dependency, Alarm Zone Delay, and Non-Latching Detection Zone functions.
5) Test each function for correction operation.
Non-latching Detection Zones do not comply with EN 54-2.
9.2.
Detection Devices
To commission the detection devices installed and connected to the control and indicating equipment,
undertake the detection device tests specified in 5.4.2.
When testing devices, the Alarm Condition will be affected by Alarm Dependency, Alarm
Zone Delay and Non-Latching Detection Zones configured for the system.
Non-latching Detection Zones do not comply with EN 54-2.
9.3.
Alarm Devices
To commission the alarm devices installed and connected to the control and indicating equipment, undertake
the following actions and tests:
1) Enter Access Level 2.
2) Press SILENCE/ACTIVATE ALARMS button. Check that the SILENCE/ACTIVATE ALARMS LED flashes
and the ACK LED flashes.
3) Press the ACK button to confirm. Check that the ACK LED is off, that the alarm devices operate, and that
the SILENCE/ACTIVATE ALARMS LED is on.
4) Press SILENCE/ACTIVATE ALARMS button. Check that the SILENCE/ACTIVATE ALARMS LED flashes
and the ACK LED flashes.
5) Press the ACK button to confirm. Check that the ACK LED is off, that the alarm devices silence, and that
the SILENCE/ACTIVATE ALARMS LED is off.
6) To exit to Access Level 2, press HOME. The ACK LED will flash.
7) Press the ACK button to confirm. Check that the ACK LED is off.