12. SPECIFICATIONS

12.1. Technical Data

Power Supply
Operating voltage
Mains supply current limit
Mains supply fuse
Mains supply fault threshold voltage
Power supply
Quiescent current (I
)
min
Maximum continuous output current (I
Maximum short-duration output current (I
Standby battery maximum capacity (2 × DC 12 V)
Maximum battery current draw
Battery fuse
Battery fault threshold voltage
Battery fault threshold internal resistance (R
Quiescent current
Detection Zones
Detection zone circuits
Number of connected devices per detection zone circuit
Detector zone quiescent current
Detector zone alarm current
Detector zone wiring characteristics (max)
Detection zone end-of-line capacitor
Manual call point resistor value
Alarm Zones
Alarm zone outputs
Alarm zone current
Alarm zone end-of-line resistor
Alarm zone monitoring
Alarm zone voltage (max)
Alarm zone fuse
Ancillary Outputs
Number of programmable output relays
Ancillary fire C/O relay
Ancillary fault N/C relay
Auxiliary supply
Auxiliary supply at (I
)
b, min
Ancillary Inputs
Evacuation start / stop
Day / Night mode
Remote reset
All specifications and other information shown were current at the date of publication and subject to change without notice.
4001 non-addressable control and indicating equipment
)
a, max
)
b, max
)
I, max
23
© 2015 ~ 2018 Ambest Electronics (Ningbo) Co Ltd. All rights reserved.
Installation and Service Manual
4001-01
4001-02
AC (85 ~ 260) V / 50/60 Hz
720 mA @ AC 230 V
4 A / AC 250 V slow blow (20 mm)
≤ AC 60 V
2.2 A @ DC 28.5 V
45 mA
0.425 A
1.3 A
7.2 Ah
1.5 A @ maximum operating temperature
6 A resettable (electronic fuse)
< DC 20 V
0.5 Ω
45 m A @ DC 28 V
2
4
32
5 mA
40 mA
80 mA
40 Ω / 0.47 µF
10 µF / DC 50 V
(470 ~ 689) Ω
1
700 mA
100 kΩ
Open- and short-circuit
DC 27.5 V
1.1 A resettable (electronic fuse)
2
2 × (1.0 A @ DC 30 V / 1 A @ AC 240 V)
1.0 A @ DC 30 V / 1 A @ AC 240 V
DC (12.0 ~ 28.2) V @ 200 mA
DC (19.5 ~ 29.0) V @ 0 mA
Non-latching, voltage-free
Non-latching, voltage-free
Non-latching, voltage-free
4001-03
8
160 mA
32-0002-r12_2018-09