5.5.

Test Condition

Tests can be conducted by a single person. To enter the Test Condition and undertake tests of the 4001 and
connected devices, follow these steps:
5.5.1. Indicator Test
1) Enter Access Level 1 or Access Level 2.
2) Press the INDICATOR TEST button. The internal sounder will operate. All LED indicators on the control
and indicating equipment and any connected remote displays will illuminate until the INDICATOR TEST
button is released.
5.5.2. Device Test
1) Enter Access Level 3.
2) Press INDICATOR TEST button. The TEST LED and the ACK LED will flash. B 1 LED will be on.
3) Press the NEXT button to select the alarm zone to test. The alarm zone will be indicated on LEDs B 1 ~ B 8.
4) Press the ACK button to confirm. The TEST LED will be on steady and the FAULT TEST DISABLE LED of
the selected Zone will flash.
5) Test a device connected to each detection zone. Upon activation of the device:
the FIRE LED will illuminate for 5 s;
the Detector Zone indicator will illuminate for 5 s;
any connected remote display Detection Zone indicator will illuminate for 5 s; and
the internal sounder, and alarm devices will operate for 1 s.
Zones will automatically reset after 10 s.
6) At the completion of the tests and to exit the Test Condition, press the INDICATOR TEST button. The TEST
LED will flash and the ACK LED will flash.
7) Press the ACK button to confirm. The ACK LED will be off. The TEST LED in the STATUS section and the
TEST FAULT DISABLED LEDs in the ZONES section will be off. The control and indicating equipment will
remain in Access Level 3.
5.6.

Delays Active/Inactive

To inhibit pre-configured delays to the Alarm Condition, take the following actions:
1) When the Alarm Condition is not present, enter Access Level 2.
2) Press the DELAYS ACTIVE button. The DELAYS ACTIVE LED will flash, and the ACK LED will flash.
3) Confirm the selection by pressing the ACK button. The ACK LED will be off and the DELAYS ACTIVE LED
will be off. The control and indicating equipment will remain in Access Level 2.
In the Alarm Condition, delays can be disabled at Access Level 1.
If an alarm is waiting to be processed when the delays are disabled, the control and
indicating equipment will immediately enter the Alarm Condition.
For the Delays Active/Inactive function, the zones must first be configured to enable
the delay at Access Level 3.
If the delay function is not set, the DELAYS ACTIVE LED will not light.
5.7.

Inactivity Timeouts

Timeouts are set to revert to Access Level 1 if there is not activity, and for system safety in the event that the
system is left without restoring it to Access Level 1. The following timeouts apply:
Enable Access Level passcode: No action for 20 s causes return to Access Level 1.
When in Access Level 2:
Enter Access Level 2 passcode: No action for 20 s causes return to Access Level 1.
When performing functions in Access Level 2, no manual input for 20 s causes the process to be
cancelled. The control and indicating equipment will return to Access Level 2.
With no specific function selected, no manual input for 1 h causes return to Access Level 1.
When in Access Level 3:
Enter Access Level 3 passcode: No action for 20 s causes return to Access Level 1.
No activity (eg a button press) for 1 h causes return to Access Level 1.
When in Device Test mode, no activity for 4 h causes return to Access Level 1.
All specifications and other information shown were current at the date of publication and subject to change without notice.
4001 non-addressable control and indicating equipment
9
© 2015 ~ 2018 Ambest Electronics (Ningbo) Co Ltd. All rights reserved.
Installation and Service Manual
32-0002-r12_2018-09

Hide quick links:

Advertisement

Table of Contents
loading

Related Products for Numens 4001 Series

This manual is also suitable for:

4001-014001-024001-03

Table of Contents