Repeater Output; Pre-Commissioning - Numens 4001 Series Installation And Service Manual

Non-addressable 2, 4, 8 zone fire alarm control and indicating equipment
Hide thumbs Also See for 4001 Series:
Table of Contents

Advertisement

Z1
Z2
Z3

6.13. Repeater Output

The repeater output connects to the 4001-04 8-zone Repeater Panel. The Repeater displays the status and
provides control of the fire detection and alarm system. The 6001-03 Network Interface Card must first be fitted
to the control and indicating equipment to provide the signaling interface to the Repeater Panels. The 4001
supports up to 7 Repeater Panels.
This interface has not been assessed for conformance with EN 54-2.
Connect the 6001-03 Network Interface Card to the DATA port on the main board, as shown below.
Install cabling from the 4001 Repeater Panel to the 6001-03 Network Interface Card. Terminate the wiring for
each indicator to their respective terminals, and the cable screens connected to earth.
Z1
Z2
Z3

7. PRE-COMMISSIONING

Prior to commissioning, undertake the following pre-commissioning checks.
1) Check the wiring for continuity. Short- or open-circuit indications must be rectified before connecting to the
control and indicating equipment. All cable testing must be carried out with a multi-meter, not a meg-ohm
meter when devices are connected. Induced voltages greater than DC 1 V indicates possible cable
problems or bad earth connection and must be rectified before device connection.
2) Check detection zone cables and ensure all field connections are made, and devices are connected to
their bases.
3) Check that all end-of-line devices are fitted, either to the last device on the detection zone circuit, the last
device on the alarm zone circuit, or to the output terminals (where the zone circuit is not used).
4) Check the earth connection is secure.
All specifications and other information shown were current at the date of publication and subject to change without notice.
4001 non-addressable control and indicating equipment
From detection zone output card
Z4
Z5
Z6
Z7
Z8
MPX
From repeater panel
Z4
Z5
Z6
Z7
Z8
MPX
© 2015 ~ 2018 Ambest Electronics (Ningbo) Co Ltd. All rights reserved.
Installation and Service Manual
S1
AUX
FIRE
FLT
C
NC
NO
C
NC NO
C
DATA
S1
AUX
FIRE
FLT
C
NC NO
C
NC
NO
C
DATA
14
INPUTS
RESET AUX SP
NC
DE
C
DV
INPUTS
RESET
AUX SP
NC
DE C
DV
32-0002-r12_2018-09

Hide quick links:

Advertisement

Table of Contents
loading

Related Products for Numens 4001 Series

This manual is also suitable for:

4001-014001-024001-03

Table of Contents