Profibus Dp Interface; Fig. 7-8: Profibus Dp Interface; Fig. 7-9: Parameters For Profibus Dp Line; Fig. 7-10: Maximum Segment Length In Relation To The Transmission Rate - Bosch Rexroth IndraControl VDP 16.1 Series Project Planning Manual

Hide thumbs Also See for Rexroth IndraControl VDP 16.1 Series:
Table of Contents

Advertisement

7-6
Interfaces

PROFIBUS DP Interface

XDPSLAVE – PROFIBUS DP
Interface
Transmission rate in kbits/s
Max. segment length in m
Optionally, the connection XDPSLAVE provides a PROFIBUS DP SLAVE
interface according to DIN EN 50170, Part 2. This interface allows to
request the states of the M-Keys available for devices with keypad (see
section M-Keys in chapter 6 on page 6-6 and 6-10).
D-Sub female connector, 9-pin
Type:
Cable type:
Transmission rate:
1
6
Fig. 7-8:
PROFIBUS DP interface
The bus cable is specified as cable type A according to EN 50170, part 8-
2. It must comply with the following cable parameters:
Surge impedance at a frequency
within a range from 3 to 20 MHz
Operating capacity
Loop resistance
Outside diameter
Core cross-section
Fig. 7-9:
Parameters for PROFIBUS DP line
The above mentioned cable parameters of a standard cable of cable type
A result in the following length extensions of a bus segment for the
particular transmission rates:
9,6
19,2
45,45
1200
1200
1200
Fig. 7-10:
Maximum segment length in relation to the transmission rate
Note:
The respective PROFIBUS Slave address is set via the rotary
switch (see page 7-1). The corresponding GSD file is
Rx010135.gsd.
VDP 16.1, VDP 40.1 and VDP 60.1
RS485
Shielded, twisted pair
10 or 100 Mbits/s
XDPSLAVE
5
DP-H
REPEATER-H
GND-DATA
U PLUS 100 mA
9
DP-L
REPEATER-L
(GND-Data)
Shield applied to the metal housing
of the plug-in connection
135 to 156 ohms
≤ 30 pF/m
≤ 110 ohms/km
> 0.64 mm
> 0.34 mm²
93,75
187,5
500
1200
1000
400
DOK-SUPPL*-VDP16/40/60-PR02-EN-P
1
2
3
4
5
6
7
8
9
DP_Bus.FH9
1500
3000
6000
200
100
100
12000
100

Hide quick links:

Advertisement

Table of Contents
loading