R 02/92
8–Bit Analog Output:
Output Signal Range . . . . . . . . . . . . . . . . . . . . .. ...0 V to +10 V, unipolar
Number of Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Digital Representation of
Output Signal . . . . . . . . . . . . . . . . . . . . . . . . .. ......8 bits
Galvanic Isolation . . . . . . . . . . . . . . . . . . . . . . . . . . . . no
Output Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . *5 mA
Burden Resistance . . . . . . . . . . . . . . . . . . . . ... ... .>2 kQ
Burden Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . burden connected to O V
Short-Circuit Protection . . . . . . . . . . . . . . . . . . . . . . temporary
Short-Circuit Current . . . . . . . . . . . . . . . . . . . . . . . . . undefined
Of
Rated Output Value for a
Cable Length of 20 M . . . . . . . . . . . . . . . . . . . . . . . . . 10 psec.
Basic Error Limit (DIN 43765) . . . . . . . . . . . . . . . . . . s*2%
Operational Error Limit
(between 0° C and +55° C) (DIN 43765) . . . . . . . . s*4%
Maximum Permissible Cable Length
–Shielded . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20m
Analog Output Amplifier
Output Signal Range . . . . . . . . . . . . . . . . . . . . . . . . . A1OV bipolar
Number of Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Galvanic Isolation . . . . . . . . . . . . . . . . . . . . . . . . . . . . no
Output Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .i5 mA
Burden Resistance . . . . . . . . . . . . . . . . . . . . . .. ....22 kQ
Burden Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . burden connected to O V
Short-Circuit Protection . . . . . . . . . . . . . . . . . . . . . . yes
Short-Circuit Current . . . . . . . . . . . . . . . . . . . . . . . . . approximately 20 mA
Maximum Permissible Cable Length
–Shielded . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20m
8–Bit Analog Output with Analog Amplifier Series:
Output Signal Range . . . . . . . . . . . . . . . . . . . . . . . ..0 Vto 10 Y unipolar
Number of Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Digital Representation . . . . . . . . . . . . . . . . . . . . . . . . 8 bits
Galvanic Isolation . . . . . . . . . . . . . . . . . . . . . . . . . . . . no
Output Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . L5 mA
Burden Resistance . . . . . . . . . . . . . . . . . . . . . . .. ....22 k!2
Burden Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . burden connected to O V
Short-Circuit Protection . . . . . . . . . . . . . . . . . . . . . . yes
Short-Circuit Current . . . . . . . . . . . . . . . . . . . . . . . . . approximately 20 mA
Settling Time to 99% of Rated Output
Value for a Cable Length of 20 M . . . . . . . . . . . . . . . 10 psec.
Error Limit at 25° C . . . . . . . . . . . . . . . . . . . . . . . . . . . s ~0.2%
Error Limit between 0° C and +55° C s tO.4Y0
Maximum Permissible Cable Length
–Shielded . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20m
243
Equipment Manual
Technical Specifications
6 – 3