■ Room temperature control for indoor unit sensor
Depending on the installed environment, correction of the room temperature sensor may
be required.
Select the appropriate control setting according to the installed environment.
The temperature of the room temperature sensor is corrected as follows:
Corrected temp. = Temp. of room temp. sensor - correction temp. value
Example of correction :
When the temperature of room temp. sensor is 78 °F and the setting value is
"03" (-2 °F), the corrected temp. will be 80 °F (78 °F [-2 °F]).
The temperature correction values show the difference from the "Standard setting" (00)
(manufacturer's recommended value).
Setting
Function number
value
30
31
(For cooling)
(For heating)
■ Room temperature control for wired remote controller sensor
Depending on the installed environment, correction of the wire remote temperature sensor
may be required.
Select the appropriate control setting according to the installed environment.
To change this setting, set Function 42 to "Both" (01).
Ensure that the Thermo Sensor icon is displayed on the remote controller screen.
Setting
Function number
value
35
36
(For cooling)
(For heating)
■ Setting record
• Record any changes to the settings in the following table.
Function
Setting Description
number
95
Heat Insulation condition (building insulation)
30
Room temperature control for indoor unit sen-
sor
31
35
Room temperature control for wired
remote controller sensor
36
After completing the Function setting, be sure to disconnect the power and reconnect it
again.
En-10
(♦... Factory setting)
Setting description
00
Standard setting
01
No correction 0 °F (0.0 °C)
02
-1 °F ( -0.5 °C)
03
-2 °F (-1.0 °C)
04
-3 °F (-1.5 °C)
05
-4 °F (-2.0 °C)
06
-5 °F (-2.5 °C)
07
-6 °F (-3.0 °C)
08
-7 °F (-3.5 °C)
09
-8 °F (-4.0 °C)
10
+1 °F (+0.5 °C)
11
+2 °F (+1.0 °C)
12
+3 °F (+1.5 °C)
13
+4 °F (+2.0 °C)
14
+5 °F (+2.5 °C)
15
+6 °F (+3.0 °C)
16
+7 °F (+3.5 °C)
17
+8 °F (+4.0 °C)
(♦... Factory setting)
Setting description
00
No correction
01
No correction 0 °F (0.0 °C)
02
-1 °F ( -0.5 °C)
03
-2 °F (-1.0 °C)
04
-3 °F (-1.5 °C)
05
-4 °F (-2.0 °C)
06
-5 °F (-2.5 °C)
07
-6 °F (-3.0 °C)
08
-7 °F (-3.5 °C)
09
-8 °F (-4.0 °C)
10
+1 °F (+0.5 °C)
11
+2 °F (+1.0 °C)
12
+3 °F (+1.5 °C)
13
+4 °F (+2.0 °C)
14
+5 °F (+2.5 °C)
15
+6 °F (+3.0 °C)
16
+7 °F (+3.5 °C)
17
+8 °F (+4.0 °C)
Cooling
Heating
Cooling
Heating

6. TEST RUN

■ Check items
(1) Is operation of each button on the remote control unit normal?
(2) Does each lamp light normally?
(3) Do air fl ow direction louvers operate normally?
(4) Is the drain normal?
(5) Do not have an abnormal noise and vibration during operation?
 Do not operate the air conditioner in test run for a long time.
■ Operation method
Before starting the test run, wait for 1 minute after connecting the power supply.
By the wireless remote controller
 To start the test run, press [START/STOP(
by using the tip of a ballpoint pen or other small object.
By the indoor unit
 To start the test run, keep on pressing the indoor unit button for more than 10 seconds.
 To end test operation, press the remote controller [START/STOP(
(When the air conditioner is running by pressing [TEST RUN], the "OPERATION" Lamp
and "TIMER" Lamp will simultaneously fl ash slowly.)
More
Cooling

7. FINISHING

Less
Heating
(1) Insulate between pipes.
• Insulate suction and discharge pipes separately.
• For rear, right, and bottom piping, overlap the connection pipe heat insulation and
indoor unit pipe heat insulation and bind them with vinyl tape so that there is no gap.
(2) Temporarily fasten the connection cable along the connection pipe with vinyl tape.
(Wrap to about 1/3 the width of the tape from the bottom of the pipe so that water
does not enter.)
(3) Fasten the connection pipe to the outside wall with a saddle, etc.
Less
(4) Fill the gap between the outside wall pipe hole and the pipe with sealer so that rain
Cooling
water and wind cannot blow in.
More
(5) Fasten the drain hose to the outside wall, etc.
Heating
(6) Check the drainage.
Pipe
Connection pipe
(heat insulation)
Bind the pipes together
so that there is no gap.
More
Cooling
Less
Heating
GOOD
Less
Cooling
More
Heating
(7) Open the intake grille of the indoor unit. Set an air cleaning fi lter (accessories)
to each fi lter folder (accessories) and attach to the air fi lter. For details of how to
assemble the air fi lter, please refer to the operating manual.

8. CUSTOMER GUIDANCE

Setting Value
Explain the following to the customer in accordance with the operating manual:
(1) Starting and stopping method, operation switching, temperature adjustment, timer, airfl ow
switching, and other remote control unit operations.
(2) Air fi lter removal and cleaning, and how to use the air louvers.
(3) Give the operating manual to the customer.
)], [TEST RUN] on the remote controller
Saddle*
Wall
Overlap the insulation
Vinyl tape*
Pipe
Wrap with cloth tape.
Cloth tape (accessory)
Drain hose
PROHIBITED
Drain hose
Saddle
Lifted up
)].
Outside wall cap*
Sealer putty*
(Outdoors)
*Locally purchased
Indoor unit pipe
(heat insulation)
Wave
End in water