3.4.2. How to the install the connection cable
(1) Remove the screws, then remove the conduit holder.
(2) Fasten the indoor unit wire harness to the conduit holder using the lock nut.
IMPORTANT: Refer to "3.4.1. Wiring system diagram" about the length of indoor unit
wire harness.
(3) Use the screws to install the conduit holder provide with the indoor unit.
(4) Remove the screws, then remove the cable clamper.
(5) Connect indoor unit wire harness to the terminal.
Refer to "3.4.1. Wiring system diagram".
(6) Use the screws to install the cable clamper.
Lock nut
Conduit holder
Screw
3.4.3. Indoor unit wiring
(1) Remove the intake grille. (Refer to "3.2.1. Intake grille removal and installation".)
(2) Remove the tapping screw for the wire cover and the wire cover A.
Wire cover A
Screw
(3) Remove the tapping screw and while minding the cable clamp hook, remove the cable
clamp.
Cable clamp
Screw
3.4.4. How to connect wiring to the terminals
■ Caution when wiring cable
Caution when wiring cable
When stripping off the insulation of a lead wire, always use a special tool such as a wire
stripper. If there is no special tool available, carefully strip the insulation with a knife etc.
(1) Use ring terminals with insulating sleeves as shown in the following fi gure to connect
to the terminal block.
(2) Securely clamp the ring terminals to the wires using an appropriate tool so that the
wires do not come loose.
Strip: 3/8 in (10 mm)
(3) Use the specifi ed wires, connect them securely, and fasten them so that there is no
stress placed on the terminals.
(4) Use an appropriate screwdriver to tighten the terminal screws. Do not use a screw-
driver that is too small, otherwise, the screw heads may be damaged and prevent the
screws from being properly tightened.
Conduit connector
Ring terminal
Sleeve
(5) Do not tighten the terminal screws too much, otherwise, the screws may break.
Screw with special washer
Ring terminal
Wire
Terminal blocks
(6) Refer to the following table for the terminal screw tightening torques.
Tightening torque [lbf·in (N·m)]
M3.5 screw
M4 screw
M5 screw
• Attach the cable clamp fi rmly by holding the connection cable, and make sure that the
clamp is fi xed securely.
Incomplete attachment of the cable clamp might cause a malfunction of the open
panel.
• Match the terminal block numbers and connection cable colors with those of the
outdoor unit or branch box.
Erroneous wiring may cause burning of the electric parts.
• Connect the connection cables fi rmly to the terminal block. Imperfect installation may
cause a fi re.
• Always fasten the outside covering of the connection cable with the cable clamp.
(If the insulator is chafed, electric discharge may occur.)
• Always connect the earth (ground) wire.
• Do not use the earth (ground) screw of the indoor unit for the connection other than a
specifi ed outdoor unit.

3.5. Remote controller installation

• Check that the indoor unit correctly receives the signal from the remote controller, then
install the remote controller holder.
Select the remote controller holder selection site by paying careful attention to the
following:
- Avoid places in direct sunlight.
- Select a place that will not be affected by the heat from a stove, etc.
3.5.1. Remote controller holder installation
 Install the remote controller a maximum distance of 22 ft. (7 m) from the remote control
receiver. However, when installing the remote controller, check that it operates cor-
rectly.
 Install the remote controller holder to a wall, pillar, etc. with the tapping screw.
Remote controller
holder fi xing
Remote
controller holder
Tapping screws
(small, acces-
sories)
3.5.2. Remote controller custom setting
Use the following steps to select the custom code of the remote controller. (Note that
the air conditioner cannot receive a signal if the air conditioner has not been set for the
matching custom code.)
(1) Press [START/STOP (
)] until only the clock is dis-
played on the remote controller display.
(2) Press [MODE] for at least 5 seconds to display the cur-
rent custom code (initially set to A).
(3) Press [TEMP. (
/
)] to change the custom code
A↔B↔C↔D
between
.
Match the code on the display to the air conditioner
custom code.
(4) Press [MODE] again to return to the clock display. The
custom code will be changed.
• If no buttons are pressed within 30 seconds after the custom code is displayed, the
system returns to the original clock display. In this case, start again from step 1.
• The air conditioner custom code is set to A prior to shipment.
Screw with special washer
Ring terminal
Wire
7.0 to 8.8 (0.8 to 1.0)
10.6 to 15.9 (1.2 to 1.8)
17.7 to 26.5 (2.0 to 3.0)
CAUTION
CAUTION
Remote controller
mounting
(1) Set
Remote
controller
(2) Down
En-7