GMI D5015SS Instruction Manual

GMI D5015SS Instruction Manual

Sil 2 repeater power supply hart, din-rail and termination board
Hide thumbs Also See for D5015SS:

Advertisement

D5015SS - D5015SK
INSTRUCTION MANUAL
SIL 2 Repeater Power Supply Hart,
DIN-Rail and Termination Board
Models D5015SS, D5015SK
D5015 - SIL 2 Repeater Power Supply
G.M. International ISM0397-3

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the D5015SS and is the answer not in the manual?

Questions and answers

Summary of Contents for GMI D5015SS

  • Page 1 D5015SS - D5015SK INSTRUCTION MANUAL SIL 2 Repeater Power Supply Hart, DIN-Rail and Termination Board Models D5015SS, D5015SK D5015 - SIL 2 Repeater Power Supply G.M. International ISM0397-3...
  • Page 2: Technical Data

    Characteristics General Description: The single channel Repeater Power Supply, D5015SS and D5015SK modules, is a high integrity analog input interface suitable for applications requiring SIL 2 level (according to IEC 61508:2010 Ed.2) in safety related systems for high risk industries.
  • Page 3: Ordering Information

    Ordering Information Power Bus and DIN-Rail accessories: Model: D5015 Connector JDFT049 Cover and fix MCHP196 1 channel source output Terminal block male MOR017 Terminal block female MOR022 1 channel sink output Front Panel and Features  SIL 2 (low demand mode of operation) according to IEC 61508:2010 Ed.2 with Tproof = 13 / 20 yrs (≤ 10 / >10 % of total SIF). ...
  • Page 4 Parameters Table In the system safety analysis, always check the Hazardous Area/Hazardous Locations devices to conform with the related system documentation, if the device is Intrinsically Safe check its suitability for the Hazardous Area/Hazardous Locations and group encountered and that its maximum allowable voltage, current, power (Ui/Vmax, Ii/Imax, Pi/Pi) are not exceeded by the safety parameters (Uo/Voc, Io/Isc, Po/Po) of the D5014 series Associated Apparatus connected to it.
  • Page 5: Function Diagram

    CLASS II, DIVISION 1, GROUPS E, F, G, CLASS III, DIVISION 1, GROUPS A, B, C, D T-Code T4, CLASS I, ZONE 2, GROUP IIC T4 CLASS I, ZONE 0, GROUP IIC MODEL D5015SS Supply 24 Vdc 2 Wire Tx...
  • Page 6: Operation

    Warning D5015 series are isolated Intrinsically Safe Associated Apparatus installed into standard EN/IEC60715 TH 35 DIN-Rail located in Safe Area or Zone 2, Group IIC, Temperature T4 or Class I, Division 2, Group A, B, C, D, T4 Hazardous Area within the specified operating temperature limits Tamb -40 to +70 °C, and connected to equipment with a maximum limit for power supply Um of 250 Vrms or Vdc.

This manual is also suitable for:

D5015sk

Table of Contents