Sil 3 - sil 2 quad channel power supply for hazardous area equipment din-rail (9 pages)
Summary of Contents for GMI D6014S
Page 1
D6014S - D6014D INSTRUCTION MANUAL SIL 3 Repeater Power Supply Hart, DIN-Rail and Termination Board, Models D6014S, D6014D D6014 - SIL 3 Repeater Power Supply G.M. International ISM0210-2...
Characteristics General Description: The single and dual channel Repeater Power Supply, D6014S and D6014D module is a high integrity analog input interface suitable for applications requiring SIL 3 level (according to IEC 61508:2010 Ed.2) in safety related systems for high risk industries. Provides a fully floating dc supply for energizing conventional 2 wires 4-20 mA, active or passive, transmitters and repeats the current in floating circuit to drive a load.
Ordering Information Power Bus and DIN-Rail accessories: Model: D6014 Connector JDFT049 Cover and fix MCHP196 1 channel Terminal block male MOR017 Terminal block female MOR022 2 channels Front Panel and Features SIL 3 according to IEC 61508:2010 Ed.2 for Tproof = 1 / 10 yrs (≤10% / >10 % of total SIF). ...
Source I Source V Sink I In 2 Out 2 (SIL 3) Termination board Power Bus connector MODEL D5014S MODEL D6014S Supply 24 Vdc Out (SIL 3) 2 Wire Tx External Powered Tx Source I Source V Sink I Termination...
Page 5
Function Diagram MODEL D5014D Duplicator MODEL D6014D Duplicator Supply 24 Vdc Out 1 (SIL 3) 2 Wire Tx Source I Source V Sink I In 1 Source I Source V Sink I Out 2 (SIL 3) Termination board Power Bus connector Connections for Duplication of 2 wires Transmitter Input Restriction on specifications for 2 wires Transmitter Input:...
Page 6
Function Diagram MODEL D5014D Duplicator MODEL D6014D Duplicator Supply 24 Vdc External Source V Sink I Powered Tx Source I In 1 Out 1 (SIL 3) Source I Source V Sink I Out 2 (SIL 3) Termination board Power Bus connector Connections for Duplication of Active Input Signal Restriction on specifications for external powered Transmitter:...
On the section “Function Diagram” and enclosure side a block diagram identifies all connections. Identify the number of channels of the specific card (e.g. D6014S is a single channel model and D6014D is a dual channel model), the function and location of each connection terminal using the wiring diagram on the corresponding section, as an example: Connect 24 Vdc power supply positive at terminal “5”...
Page 8
Ch1 1-5 V Ch2 1-5 V (on 250 (on 250 Ω Ω internal shunt) internal shunt) D6014S Source mode is factory settings Only Source/Sink mode can be used for SIL applications. Dip switch configuration ON ON OFF OFF 4-20 mA...
Need help?
Do you have a question about the D6014S and is the answer not in the manual?