Download Print this page
Parker SC Series Service Bulletin

Parker SC Series Service Bulletin

Solenoid valve

Advertisement

Quick Links

Service Bulletin 33-00C
SOLENOID Valve -- Type SC
Port Size 9 - 66mm (3/8" - 2-5/8")
For , R12, R22, R502 and other common refrigerants
FEATURES
Pilot Operated
Interchangeable Capacity Cartridges Same
as Used on (S)PORT EPR's
Low Pressure Drop
Manual Opening Stem
All Service from the Top
Sweat-in-place Without Disassembly
Maximum Opening Pressure Difference
(MOPD): 20.7 bar (300 psig)
Design Pressure (MRP): 31.0 bar (450 psig)
Molded Class "F" Coil Construction
Pilot Light Available
DESCRIPTION
The new SC suction solenoid for commercial applications
was developed by the Refrigerating Specialties Division
of Parker Hannifin as an alternative low pressure drop
shut off valve in a wide range of both port and connection
sizes. With cartridge (port) sizes available as large as 2-
5/8", SC solenoids are capable of handling greater flow
rates than other commercially available valves for suction
applications in a non-flanged design. In addition, this
unique design incorporates the same concept of cartridge
interchangeability as found in Parker's popular (S)PORT
evaporator pressure regulators.
This innovative design actually utilizes the same capacity
cartridges (and valve bodies) as those used with the
(S)PORT regulator series, as well as the same solenoid
actuator, solenoid coil, and splice box coil housing.
Capacity cartridges can be changed by simply unscrewing
the valves' four bonnet bolts in order to remove the
adapter and cartridge assemblies. With this flexible line
of solenoid valves now supplementing the existing line of
050414
Figure 1
August 2005 Installation, Service and Parts Information
(S)PORT regulators having these same characteristics, a
single reliable source for all suction line components is
now available
This ductile iron-bodied solenoid valve with
.
brazed copper couplings is suitable for most common
refrigerants, certain oils and other fluids approved for use
in refrigeration. This valve may be opened by means of a
manual opening stem for servicing or in case of electrical
power failure. These solenoids are an integrated assembly
of (3) three modules: 1) A body containing no moving
parts; 2) A capacity cartridge, which contains both piston
and modulating plug, and 3) an adapter on which the pilot
solenoid is mounted and which incorporates a manual
opening stem which bypasses the pilot pressure around
the solenoid and directs it to the top of the valve piston.
ORDERING GUIDE
Parker's SC solenoid series can be ordered using the
same numbering system which is used with (S)PORT
pressure regulators. The first two digits following the
"SC" valve type designate the valve's port size in eighths
of an inch, while the second two digits designate the
connection
also in eighths of an inch. For example, an
size,
SC-07-09 would call for a 7/8" Port (or cartridge) size and
a 1-1/8" ODS connection. Both (S)PORT regulators and SC
solenoids are frequently ordered less coil and coil housing
for inventory purposes. Should a solenoid coil be desired
however, please indicate the voltage requirement when
ordering.
PRINCIPLES OF OPERATION
The R/S Type SC is a pilot operated solenoid. The valve
in its closed position, with the solenoid coil de-energized
and the plunger and piston plug in the seated position, is
shown in Figure 1. Electrical energizing of the solenoid
coil forms a magnetic field, pulling up the plunger, lifting
it off its seat. Upward motion of the plunger permits
entrance of the fluid from the valve inlet
ISO 9001-2000 CERTIFIED

Advertisement

loading

Summary of Contents for Parker SC Series

  • Page 1 Refrigerating Specialties Division brazed copper couplings is suitable for most common of Parker Hannifin as an alternative low pressure drop refrigerants, certain oils and other fluids approved for use shut off valve in a wide range of both port and connection in refrigeration.
  • Page 2 flow. The pressure difference across the valve, standard on Parker Refrigerating Specialties Division acting upon the area of the valve seat, plus the force of S81 and S82 solenoid valves.
  • Page 3 Service Bulletin 33-00C August 2005 Repair Kits for SC1 and SC2 Solenoid Valves Item No. Description Qty. SC1 3 thru 11 SC2 13 thru 21 Bolt Package 204677 204676 13,14,19,20,36,37 Adapter Assembly 204671 204670 Pin, Locating N/A Separately Body Assembly N/A Separately 14,17,17A,18 Cartridge Kit (3/8”) - 03...
  • Page 4 F.O.B. factory. Warranty does not pertinent product bulletins and the current Bulletin RSB cover products which have been altered or repaired in prior to installation or servicing work. Parker Hannifin Corporation Refrigerating Specialties  2445 South 25th Avenue Broadview, IL 60155-3858 USA ...

This manual is also suitable for:

Sc1Sc2