(4) Refrigerant charging calculation (R2 system)
PURY-P-YLM-A1
Sample connection (with 3 BC controller and 6 indoor units) (PURY-P700YSLM-A1)
OU
(Main unit)
H
F
Reducer (P15-P50)
(attached with BC controller)
Amount of additional refrigerant to be charged
Refrigerant for extended pipes (field piping) is not factory-charged to the outdoor unit. Add an appropriate amount of refrigerant for each pipes on site.
Record the size of each high pressure pipe and liquid pipe, and the amout of refrigerant that was charged on the outdoor unit for future reference.
Calculating the amount of additional refrigerant to be charged
The amount of refrigerant to be charged is calculated with the size of the on-site-installed high pressure pipes and liquid pipes, and their length.
Calculate the amount of refrigerant to be charged according to the formula below.
Round up the calculation result to the nearest 0.1kg. (i.e., 16.03 kg = 16.1 kg)
<Amount of additional refrigerant to be charged>
Calculating the amount of additional refrigerant to be charged
Units "m" and "kg" (In an R2 system)
<Formula>
• When the piping length from the outdoor unit to the farthest indoor unit is 30.5 m (100 ft) or shorter
Amount of
High-pressure pipe
additional
=
ø28.58 total length
charge (kg)
× 0.36 (kg/m)
Liquid pipe ø12.7
+
total length
× 0.12 (kg/m)
Total capacity of
outdoor units
P200
+
P250
P300
P350–900
Number of sub BC
controllers
+
1
2
Outdoor unit model
Single
+
Combination
OU
(Sub unit)
Outdoor Twinning kit
G
A
BC controller (Main BC)
a
Joint kit
b
IU
IU
2 : P250
1 : P50
High-pressure pipe
High-pressure pipe
+
ø22.2 total length
+
ø19.05 total length
× 0.23 (kg/m)
× 0.16 (kg/m)
Liquid pipe ø9.52
Liquid pipe ø6.35
+
total length
+
total length
× 0.06 (kg/m)
× 0.024 (kg/m)
Amount
(to be added for standard or
main BC controller)
3.0kg
4.5kg
4.5kg
6.0kg
Amount
Total capacity of connected
(to be added for sub
BC controller)
1.0kg
2.0kg
+
(to be added for
outdoor unit)
P200 to P250YLM-A1
P300 to P400YLM-A1
P450 to P500YLM-A1
P400 to P550YSLM-A1
P600 to P800YSLM-A1
P850YSLM-A1
P900YSLM-A1
Joint
C
Joint
B
c
d
IU
IU
3 : P15
4 : P20
High-pressure pipe
+
ø15.88 total length
× 0.11 (kg/m)
Main BC controller
Amount
+
HA-type
2.0kg
Amount
(to be added for
indoor units
indoor unit)
80 or below
2.0kg
81 to 160
2.5kg
161 to 330
3.0kg
331 to 390
3.5kg
391 to 480
4.5kg
481 to 630
5.0kg
631 to 710
6.0kg
711 to 800
8.0kg
801 to 890
9.0kg
891 to 1070
10.0kg
1071 to 1250
12.0kg
1251 or above
14.0kg
Amount
0kg
0kg
5.5kg
0kg
0kg
5.5kg
11.0kg
- 78 -
IU
e
5 : P140
BC controller (Sub BC)
D
BC controller (Sub BC)
E
f
IU
6 : P200
Liquid pipe ø15.88
+
total length
× 0.2 (kg/m)