Mitsubishi Electric PWFY-P100VM-E-BU Data Book page 12

Hide thumbs Also See for PWFY-P100VM-E-BU:
Table of Contents

Advertisement

(2) PWFY-EP100VM-E1-AU
Model
Power source
Heating capacity
(Nominal)
Power input
Current input
Temp. range of heating
Outdoor temp.
for outdoor unit
Circulating Water temp.
for heat source unit
Inlet Water temp.
for PWFY
Cooling capacity
(Nominal)
Power input
Current input
Temp. range of cooling
Outdoor temp.
for outdoor unit
Circulating Water temp.
for heat source unit
Inlet Water temp.
for PWFY
Connectable
Total capacity
outdoor unit
Model / Quantity
/heat source unit
Sound pressure level (measured in anechoic room)
Liquid
Diameter of
refrigerant pipe
Gas
Inlet
Diameter of
water pipe
Outlet
Field drain pipe size
External finish
External dimension H × W × D
Net weight
Circulating water
Operation Volume
Range
Design pressure
R410a
Water
External
Drawing
Wiring
Document
Standard attachment
Accessory
Optional parts
Remark
Note:
*1 Nominal heating conditions (PWFY conditions are indicated in the parentheses.)
<Y/HP (ZUBADAN)/R2-series>
Outdoor temp. : 7°CDB/6°CWB (45°FDB/43°FWB)
Pipe length : 7.5 m (24-9/16 ft.)
Level difference : 0 m (0 ft.)
(Inlet water temp. 30°C, Water flow rate 4.30 m
*2 Nominal cooling conditions (PWFY conditions are indicated in the parentheses.)
<Y/HP (ZUBADAN)/R2-series>
Outdoor temp. : 35°CDB (95°FDB)
Pipe length : 7.5 m (24-9/16 ft.)
Level difference : 0 m (0 ft.)
(Inlet water temp. 23°C, Water flow rate 3.86 m
* Due to continuing improvement, the above specifications may be subject to change without notice.
* The unit is not designed for outside installations.
* Please don't use the steel material for the water piping material.
* Please always make water circulate or add the brine to the circulation water when the ambient temperature becomes 0°C or less.
* Please always make water circulate or pull out the circulation water completely when not using it.
* Please do not use ground water and well water.
*1
kW
*1
kcal / h
*1
BTU / h
kW
A
W.B
W.B
W.B
-
-
-
*2
kW
*2
kcal / h
*2
BTU / h
kW
A
D.B
D.B
D.B
-
-
-
dB<A>
mm(in.)
mm(in.)
mm(in.)
mm(in.)
mm(in.)
mm
in.
kg(lbs)
m
/h
3
MPa
MPa
Strainer, Heat insulation material, Expansion joint, Flow switch x 1set. Buffer material.
Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and
other items shall be referred to the Installation Manual.
<WY/WR2-series>
Circulating water temp. : 20°C (68°F)
Pipe length : 7.5 m (24-9/16 ft.)
Level difference : 0 m (0 ft.)
/h)
(Inlet water temp. for PWFY side 30°C, Water flow rate 4.30 m
3
<WY/WR2-series>
Circulating water temp. : 30°C (86°F)
Pipe length : 7.5 m (24-9/16 ft.)
Level difference : 0 m (0 ft.)
/h)
(Inlet water temp. for PWFY side 23°C, Water flow rate 3.86 m
3
- 4 -
PWFY-EP100VM-E1-AU
1-phase 220-230-240V 50/60Hz
12.5
10,800
42,700
0.015
0.068 - 0.065 - 0.063
-20~32°C (-4~90°F) R2-series
-20~15.5°C (-4~60°F) Y-series
-25~15.5°C (-13~60°F) HP (ZUBADAN) -series
10~45°C (50~113°F) WR2-series
10~45°C (50~113°F) WY-series
10~40°C (50~104°F) R2/Y/HP (ZUBADAN) /WR2/WY-series
11.2
9,600
38,200
0.015
0.068 - 0.065 - 0.063
-5~46°C (23~115°F) R2-series
-5~46°C (23~115°F) Y-series
-5~43°C (23~110°F) HP (ZUBADAN)-series
10~45°C (50~113°F) WR2-series
10~45°C (50~113°F) WY-series
10~35°C (50~95°F)
50~100% of outdoor / heat source unit capacity
PUHY-P
Y(S)KB-A1(-BS)
PUHY-EP
Y(S)LM-A(-BS)
PUHY-HP
Y(S)HM-A(-BS)
PQHY-P
Y(S)HM-A
PURY-(E)P
Y(S)LM-A(1)(-BS)
PQRY-P
Y(S)HM-A
29
ø9.52 (ø3/8") Brazed
ø15.88 (ø5/8") Brazed
PT1 Screw (PT3/4 Screw without expansion joint)
PT1 Screw (PT3/4 Screw without expansion joint)
ø32 (1-1/4'')
NO
800 (785 without legs) × 450 × 300
31-1/2" (30-15/16" without legs) × 17-3/4" × 11-13/16"
33 (73)
1.8~4.30
4.15
1.00
WKJ94T340
WKE94C951
Installation Manual, Instruction Book
Solenoid valve kit: PAC-SV01PW-E
/h)
3
/h)
3
* Install the outdoor unit (R2-series) in an
environment where the wet bulb temp.
will not exceed 32°C
* The water circuit must use the closed circuit.
* Please do not use it as a drinking water.
Unit converter
kcal/h = kW × 860
BTU/h= kW × 3,412
cfm
= m
/min × 35.31
3
lbs
= kg / 0.4536
* The specification data is subject
to rounding variation.

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pwfy-ep100vm-e1-auPwfy-ep100vm-e2-au

Table of Contents